TE-RTD12 User Manual - I.C.T. Power Company Inc.
TE-RTD12 User Manual - I.C.T. Power Company Inc.
TE-RTD12 User Manual - I.C.T. Power Company Inc.
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Motortronics<br />
F026 - RTD #7 DESCRIPTION SELECTION<br />
Select RTD Description Selection (0 – 1), Default Setting: 0 – Front Bearing (Fb)<br />
Setting Assignment<br />
0 Front Bearing (Fb)<br />
1 RTD #7 (rt 7)<br />
F027 - RTD #7 FRONT BEARING ALARM <strong>TE</strong>MPERATURE (0 – 464), Default Setting: OFF<br />
Set RTD Temperature Alarm Level. When the RTD temperature reached this level Alarm “ALAr Fb” or<br />
“ALAr rt 7” is shown on the keypad display. The Level can be programmed in Celsius or Fahrenheit depending<br />
on the setting of F095.<br />
Range 0 – 240 Degrees Celsius (F095 = 0)<br />
Range 32 – 464 Degrees Fahrenheit (F095 = 1)<br />
F028 - RTD #7 FRONT BEARING TRIP <strong>TE</strong>MPERATURE (0 – 464), Default Setting: OFF<br />
Set RTD Temperature trip Level. When the RTD temperature reached this level trip “triP Fb” or “triP rt 7” is<br />
shown on the keypad display. The Level can be programmed in Celsius or Fahrenheit depending on the setting<br />
of F095.<br />
Range 0 – 240 Degrees Celsius (F095 = 0)<br />
Range 32 – 464 Degrees Fahrenheit (F095 = 1)<br />
F029 – REAR BEARING TYPE SELECTION (0 – 4), Default Setting: 0 - OFF<br />
Select RTD #8 Type<br />
Setting Type<br />
0 OFF<br />
1 100 Ohm Pt (Platinum RTD)<br />
2 10 Ohm Cu (Copper RTD)<br />
3 100 Ohm Ni (Nickel RTD)<br />
4 120 Ohm Ni (Nickel RTD)<br />
F030 - RTD #8 DESCRIPTION SELECTION<br />
Select RTD Description Selection (0 – 1), Default Setting: 0 – Rear Bearing (rb)<br />
Setting Assignment<br />
0 Rear Bearing (rb)<br />
1 RTD #8 (rt 8)<br />
F031 - RTD #8 REAR BEARING ALARM <strong>TE</strong>MPERATURE (0 – 464), Default Setting: OFF<br />
Set RTD Temperature Alarm Level. When the RTD temperature reached this level Alarm “ALAr rb” or<br />
“ALAr rt 8”is shown on the keypad display. The Level can be programmed in Celsius or Fahrenheit depending<br />
on the setting of F095.<br />
Range 0 – 240 Degrees Celsius (F095 = 0)<br />
Range 32 – 464 Degrees Fahrenheit (F095 = 1)<br />
www.motortronics.com Page 23