Motortronics<br />

F026 - RTD #7 DESCRIPTION SELECTION<br />

Select RTD Description Selection (0 – 1), Default Setting: 0 – Front Bearing (Fb)<br />

Setting Assignment<br />

0 Front Bearing (Fb)<br />

1 RTD #7 (rt 7)<br />

F027 - RTD #7 FRONT BEARING ALARM <strong>TE</strong>MPERATURE (0 – 464), Default Setting: OFF<br />

Set RTD Temperature Alarm Level. When the RTD temperature reached this level Alarm “ALAr Fb” or<br />

“ALAr rt 7” is shown on the keypad display. The Level can be programmed in Celsius or Fahrenheit depending<br />

on the setting of F095.<br />

Range 0 – 240 Degrees Celsius (F095 = 0)<br />

Range 32 – 464 Degrees Fahrenheit (F095 = 1)<br />

F028 - RTD #7 FRONT BEARING TRIP <strong>TE</strong>MPERATURE (0 – 464), Default Setting: OFF<br />

Set RTD Temperature trip Level. When the RTD temperature reached this level trip “triP Fb” or “triP rt 7” is<br />

shown on the keypad display. The Level can be programmed in Celsius or Fahrenheit depending on the setting<br />

of F095.<br />

Range 0 – 240 Degrees Celsius (F095 = 0)<br />

Range 32 – 464 Degrees Fahrenheit (F095 = 1)<br />

F029 – REAR BEARING TYPE SELECTION (0 – 4), Default Setting: 0 - OFF<br />

Select RTD #8 Type<br />

Setting Type<br />

0 OFF<br />

1 100 Ohm Pt (Platinum RTD)<br />

2 10 Ohm Cu (Copper RTD)<br />

3 100 Ohm Ni (Nickel RTD)<br />

4 120 Ohm Ni (Nickel RTD)<br />

F030 - RTD #8 DESCRIPTION SELECTION<br />

Select RTD Description Selection (0 – 1), Default Setting: 0 – Rear Bearing (rb)<br />

Setting Assignment<br />

0 Rear Bearing (rb)<br />

1 RTD #8 (rt 8)<br />

F031 - RTD #8 REAR BEARING ALARM <strong>TE</strong>MPERATURE (0 – 464), Default Setting: OFF<br />

Set RTD Temperature Alarm Level. When the RTD temperature reached this level Alarm “ALAr rb” or<br />

“ALAr rt 8”is shown on the keypad display. The Level can be programmed in Celsius or Fahrenheit depending<br />

on the setting of F095.<br />

Range 0 – 240 Degrees Celsius (F095 = 0)<br />

Range 32 – 464 Degrees Fahrenheit (F095 = 1)<br />

www.motortronics.com Page 23