4 Applications<br />

4.1 Fixed sprinkler systems<br />

Figure 14: Sprinkler installation <strong>VSH</strong> <strong>Press</strong> Sprinkler<br />

Fixed sprinkler systems are permanently<br />

installed fire extinguishing and fire protection<br />

systems, which independently detect and<br />

report a fire and automatically start the<br />

extinguishing process. The installation of<br />

the <strong>VSH</strong> <strong>Press</strong> Sprinkler system in sprinkler<br />

systems is carried out in accordance with<br />

appropriate guidelines (e.g. VdS-CEA 4001).<br />

Depending on the material installed (stainless<br />

or carbon steel), the system can either be<br />

used in wet or dry fixed sprinkler systems.<br />

<strong>VSH</strong> <strong>Press</strong> Sprinkler Galvanized is only suitable<br />

for use in fixed wet sprinkler systems,<br />

where <strong>VSH</strong> <strong>Press</strong> Sprinkler Stainless can be<br />

used in both wet and dry fixed sprinkler<br />

systems.<br />

17<br />

With different approvals under which the <strong>VSH</strong> <strong>Press</strong> Sprinkler system is installed, also different<br />

hazard classes apply.For more detailed information on applicable hazard classes, please contact<br />

your <strong>VSH</strong> representative, or <strong>VSH</strong> Fittings directly.<br />

When the <strong>VSH</strong> <strong>Press</strong> Sprinkler system is used, it should also be ensured that no loads can fall onto<br />

the tube network under normal conditions or in the case of a fire; for example ventilation ducts and<br />

cable trays should not be installed above the sprinkler tubes. Depending on your type of system<br />

and the approval which applies to your fixed sprinkler system, different fastener distances apply.<br />

In sprinkler applications the fastener distances for steel press systems are based on the values<br />

used for copper tube. Always follow the valid local guidelines and please make sure to follow<br />

these fastener distances correctly.<br />

DN Tube dimension Fastener distances (m)<br />

CEA 4001 (VdS) NFPA 13 DIN 1988-2<br />

20 22 2,00 2,44 2,00<br />

25 28 2,00 2,44 2,25<br />

32 35 2,00 3,66 2,75<br />

40 42 2,00 3,66 3,00<br />

50 54 3,00 3,05 3,50<br />

65 76,1 3,00 3,05 4,25<br />

80 88,9 3,00 3,05 4,75<br />

100 108 3,00 3,05 5,00<br />

Table 8: Fastener distances for sprinkler tubes<br />