5<br />

The sizes refer to the general installation geometries and are shown schematically<br />

in illustrations 15, 16 and 17.<br />

a<br />

d a<br />

b<br />

c<br />

b<br />

Figure 15 Figure 16 Figure 17<br />

Figure 15 Figure 16 Figure 17<br />

DN<br />

20<br />

External ø (mm)<br />

22<br />

a<br />

65<br />

b<br />

25<br />

a<br />

80<br />

b<br />

31<br />

c<br />

35<br />

d<br />

150<br />

Tube depth (mm)<br />

40<br />

25 28 75 25 80 31 35 150 60<br />

32 35* 115 75 115 75 75 265 70<br />

40 42* 120 75 115 75 75 265 70<br />

50 54* 200 85 120 85 85 290 70<br />

65 76,1* 250 170 200 170 190 390 80<br />

80 88,9* 250 170 250 170 210 460 90<br />

100 108* 250 170 250 170 210 460 100<br />

23<br />

Table 17: Space needed for installation (* press slings)<br />

5.8 Bending<br />

Depending on the system, it may be necessary to bend the tube during installation. For this, commercially<br />

available manual, hydraulic or electric bending tools with the corresponding bending<br />

segments are used. The suitability of the bending tool is defined by the manufacturer. <strong>VSH</strong> <strong>Press</strong><br />

Sprinkler tubes for sprinkler installations are cold pliable in the sizes 22 and 28 mm.<br />

The minimum bending radius is as follows:<br />

Carbon and stainless steel tube<br />

<strong>VSH</strong> <strong>Press</strong> flexible hoses<br />

Rmin = 3,5 x d (max. 28 mm)<br />

22 mm = 70 mm<br />

28 mm = 85 mm<br />

Due to the danger of corrosion the tube must not be bent when it is warm<br />

Providing suitable solutions