6.2.1 <strong>VSH</strong> <strong>Press</strong> Sprinkler Galvanized VdS<br />

VdS is a system approval, meaning that the approval<br />

is only valid when all components are combined:<br />

<strong>VSH</strong> <strong>Press</strong> Sprinkler Galvanized G4080007<br />

• <strong>VSH</strong> <strong>Press</strong> Sprinkler Galvanized fitting<br />

• <strong>VSH</strong> <strong>Press</strong> Sprinkler Galvanized tube<br />

• <strong>Press</strong> tools<br />

28<br />

VdS approval for the <strong>VSH</strong> <strong>Press</strong> Sprinkler Galvanized system was awarded in 2008. The <strong>VSH</strong><br />

<strong>Press</strong> Sprinkler Galvanized system may be used in fixed wet sprinkler systems in the hazard<br />

classes LH up to partially OH4 (theaters, concert halls, movie theaters).<br />

The approval applies to the dimensional range with a diameter DN20 up to DN100 (22-108 mm)<br />

with a maximum operating pressure of 16 bar for wet sprinkler systems. <strong>VSH</strong> <strong>Press</strong> Sprinkler Galvanized<br />

fittings are made of zinc-plated unalloyed steel, combined with a carbon-steel tube produced<br />

specifically for the <strong>VSH</strong> <strong>Press</strong> Sprinkler Galvanized system which inner and outer surface is<br />

galvanized (Sendzimir tube).<br />

6.2.2 <strong>VSH</strong> <strong>Press</strong> Sprinkler Stainless VdS<br />

<strong>VSH</strong> <strong>Press</strong> Sprinkler Stainless G4080037<br />

• <strong>VSH</strong> <strong>Press</strong> Sprinkler Stainless fitting<br />

• <strong>VSH</strong> <strong>Press</strong> Sprinkler Stainless tube<br />

• <strong>Press</strong> tools<br />

VdS recognition of the <strong>VSH</strong> <strong>Press</strong> Sprinkler Stainless system was awarded in 2008. The <strong>VSH</strong><br />

<strong>Press</strong> Sprinkler stainless system may be used in fixed wet and dry sprinkler systems in the hazard<br />

classes LH up to partially OH4 (theaters, concert halls, movie theaters).<br />

The approval applies to the dimensional range with a diameter DN20 to DN100 (22-108 mm)<br />

with an operating pressure of maximum 16 bar for wet and dry sprinkler systems. The <strong>VSH</strong> <strong>Press</strong><br />

Stainless fittings are made of 1.4404 (AISI 316L) stainless steel, the tubes are made of 1.4401<br />

(AISI 316) stainless steel.<br />

6.2.3 Assembly and installation of VdS approved sprinkler installations<br />

The assembly and installation of the <strong>VSH</strong> <strong>Press</strong> Sprinkler system may only be performed by<br />

trained technical personnel who are qualified to work on sprinkler systems, For example, the<br />

guideline CEA 4001 (VdS) contains the requirements for the assembly of a fixed sprinkler system.<br />

The company performing the installation must comply at all times with the guidelines.