4 Electrical installation<br />
4.1 Setup<br />
PROFIBUS DP consists of at least one bus segment. One segment consists of at<br />
least two but not more than 32 stations. They are all physically connected with a<br />
bus cable. One of the stations is the master. The master is the active station on<br />
PROFIBUS. It can send or request data to/from other stations. The slaves are the<br />
passive stations on PROFIBUS. They can only exchange data with the master<br />
when the master requests this.<br />
Terminating resistors must be placed at the beginning and the end of the bus.<br />
Master no. 1<br />
Slave no. 2<br />
Slave no. 3<br />
Slave no.<br />
Station (master or slave)<br />
Station with circuited<br />
terminating resistor<br />
Fig. 4-1: Setup of a bus segment<br />
If more than 32 stations are to operate on a bus or the maximum line length of a<br />
bus segment is exceeded, several bus segments must be coupled via RS 485<br />
repeaters. The maximum number of masters and slaves within one bus segment<br />
must be decreased by one for every repeater used. The maximum number of<br />
masters and slaves over the entire bus system is 126. The maximum line length<br />
depends on the baud rate being used. The table below gives you the maximum<br />
permissible lengths for one segment and for all segments.<br />
We strongly recommend NOT using stub lines in the setup. This is only permitted<br />
during commissioning. This bus system is usually set up with shielded, two-wire<br />
lines (RS 485). It can also be set up for special applications via fiber-optic<br />
conductors. STÖBER Antriebstechnik offers the coupling to the two-wire line.<br />
This permits a maximum distance of 10,000 m. When suitable measures are<br />
taken on the master side, slaves can be coupled or decoupled during operation<br />
without having to interrupt data communication on the bus.<br />