<strong>Co</strong>nfiguration of the bus system<br />

Operation manual<br />

7<br />

7.2 Procedure for SIEMENS SIMATIC S7 and STEP 7<br />

Different configuration software is used for different PROFIBUS masters. How<br />

this works with the SIMATIC Manager for the SIMATIC S7 in version 5.1 will be<br />

explained with an example. At least version 5.1 SP4 of STEP 7 is required for use<br />

of DPV1 with STEP 7. The SIMATIC S7 CPUs must also support DPV1. For<br />

whether the particular CPU supports DPV1, see the CPU characteristics under<br />

the hardware manager.<br />

7.2.1 The HW-config<br />

To link in the GSD file in the STEP 7, open the menu "Extras" "Neue GSD Datei<br />

einbinden." Then display the GSD in the device catalog under "Extras" "Katalog<br />

Aktualisieren." This must done only once. After this, the inverter appears at the<br />

position as shown on the screen (Fig. 7-1) in the hardware catalog. HW-<strong>Co</strong>nfig in<br />

STEP 7 may look like this.<br />

Fig. 7-1: HW-<strong>Co</strong>nfig<br />

It is not necessary to reserve a separate memory area for the acyclic services<br />

(DPV1). This means that no PPO type must be selected which supports PKW.<br />

Every PPO type has this capability with the DPV1 protocol.<br />