<strong>Co</strong>nfiguration of the bus system<br />
Operation manual<br />
7<br />
7.2 Procedure for SIEMENS SIMATIC S7 and STEP 7<br />
Different configuration software is used for different PROFIBUS masters. How<br />
this works with the SIMATIC Manager for the SIMATIC S7 in version 5.1 will be<br />
explained with an example. At least version 5.1 SP4 of STEP 7 is required for use<br />
of DPV1 with STEP 7. The SIMATIC S7 CPUs must also support DPV1. For<br />
whether the particular CPU supports DPV1, see the CPU characteristics under<br />
the hardware manager.<br />
7.2.1 The HW-config<br />
To link in the GSD file in the STEP 7, open the menu "Extras" "Neue GSD Datei<br />
einbinden." Then display the GSD in the device catalog under "Extras" "Katalog<br />
Aktualisieren." This must done only once. After this, the inverter appears at the<br />
position as shown on the screen (Fig. 7-1) in the hardware catalog. HW-<strong>Co</strong>nfig in<br />
STEP 7 may look like this.<br />
Fig. 7-1: HW-<strong>Co</strong>nfig<br />
It is not necessary to reserve a separate memory area for the acyclic services<br />
(DPV1). This means that no PPO type must be selected which supports PKW.<br />
Every PPO type has this capability with the DPV1 protocol.<br />
WE KEEP THINGS MOVING<br />
ID 441687.03<br />
26