Fundamentals of PROFIBUS<br />
Operation manual<br />
5<br />
In contrast to cyclic communication, acyclic communication data are only<br />
exchanged when necessary. Acyclic communication is performed either via an<br />
appropriate routine within cyclic communication (for PKW routine, see<br />
PROFIDrive profile version 2) or via the DP-V1 routines READ and WRITE. This<br />
permits the connection of commissioning tools as class-2 master (C2) to<br />
PROFIBUS.<br />
Several acyclic channels are available at the same time. The C1 master (the<br />
controller) maintains a continuously open connection to the inverter (MSAC1)<br />
which can be used as necessary by the controller program (arrow 2). In addition,<br />
the inverter provides the capacity for two connections (MSAC2) which can be<br />
established and used as necessary by C2 masters (e.g., an operator panel or a<br />
service PC).<br />
Time wise on PROFIBUS, the cyclic data always have the highest priority. During<br />
each data exchange cycle, the master inserts an acyclic telegram when<br />
necessary. This does not noticeably affect the speed of PROFIBUS.<br />
5.3.2 User data communication<br />
The process data channel is used for high-speed transmission of data which are<br />
used for controlling and monitoring the running process and which require a<br />
particularly short transmission time. When the bus system is configured, the<br />
selection of the PPO type specifies whether the cyclic parameter channel is to be<br />
used and how many bytes the process data channel will have.<br />
All parameters can be read and changed with the parameter channels. First, the<br />
PKW1 routine (which uses the acyclic services of PROFIBUS) specified by<br />
PROFIDrive version 3 is available and, second, the old PKW0 routine (which is<br />
embedded in the cyclic data) defined by PROFIDrive version 2 is offered.<br />
Because of the comprehensive capabilities and the access to all inverter<br />
parameters without exception, the new PKW1 routine should be used if possible:<br />
Transmission Channel Inverter with Option DP-V1 5000<br />
Process data reference values<br />
from the bus to the processing on<br />
the device.<br />
<strong>Co</strong>mplete processing of a PKW0<br />
service.<br />
PKW1 via acyclic services.<br />
Depends on the configuration and setting of<br />
the parameter A150 cycle time.<br />
Approx. 16 to 64 ms<br />
Depends on the configuration!<br />
Approx. 16 to 64 ms<br />
Depends on the configuration!<br />