132 PROPOSAL TO REVISE ENERGY EFFICIENCY REQUIREMENTS OF THE BUILDING CODE OF AUSTRALIA FOR COMMERCIAL BUILDINGS<br />

C Procedure for energy efficiency<br />

modelling<br />

As mentioned in the main body of the report, the energy savings<br />

associated with the proposed amendments to the BCA energy efficiency<br />

provisions were estimated using energy simulation output data provided by<br />

the ABCB. This Appendix provides additional details about the procedure<br />

used by the ABCB for modelling various energy efficiency features and<br />

defines the building forms, their systems and other criteria used. The<br />

information in this appendix was provided by the ABCB.<br />

<strong>Building</strong>s<br />

The following three buildings are considered to represent the thermal<br />

performance of most of the buildings constructed today and are sufficiently<br />

diverse to test any proposed changes to the BCA Volume One Section J.<br />

They have been modelled as BCA 2009 compliant (where current<br />

stringency is being modelled, at the limit of compliance) and as follows.<br />

a) As Greenfield sites with no over-shadowing.<br />

b) Except for the square building, all buildings were modelled with the<br />

longitudinal building axis on an east–west orientation and a north–south<br />

orientation (across both orientations the variation in the building energy<br />

use varied by less than 5 per cent).<br />

c) With glazing generally 6 mm single tinted on all four facades and with a<br />

glazing area to façade area proportion of approximately 40 per cent<br />

adjusted to just comply with Section J2 without projections, external<br />

shading devices or reveals. The glazing was modelled with internal<br />

Venetian blinds with a shading attenuation coefficient of 0.74. Venetian<br />

blinds were assumed closed on weekdays when the solar radiation<br />

exceeds 170 W/m 2 and assumed open at other times.<br />

d) With the air conditioning systems.<br />

e) Specifically selected as being typical for each building form as<br />

described below.<br />

f) Details as described under Services Details.<br />