3.Dispatch Information<br />

IMO_MAN_0024<br />

217 AGC dispatch messages may be sent in one of two forms:<br />

(1) Dispatch Message Body – Regulation with Range Dispatch Only: will include<br />

the following fields:<br />

Persistent Resource<br />

DISPATCH_TYPE = „RGR‟<br />

Startstop = „Start‟<br />

RESOURCE_ID<br />

REGULATION_RANGE = The regulation range in MW expected<br />

from the resource.<br />

DELIVERY_START_TIME<br />

DELIVERY_STOP_TIME<br />

(2) Dispatch Message Body – Regulation with Range and Fixed Base-Point<br />

Dispatch: will include the following fields:<br />

Persistent Resource<br />

DISPATCH_TYPE = „RGS‟<br />

Startstop = „Start‟<br />

RESOURCE_ID<br />

AMOUNT = The fixed base point in MW that the unit will operate at<br />

while on AGC.<br />

REGULATION_RANGE = The regulation range in MW expected<br />

from the resource.<br />

DELIVERY_START_TIME<br />

DELIVERY_STOP_TIME<br />

218 For details of the Dispatch Message Structures and sample examples of all the<br />

message types, please refer to the “Web Based Message Exchange – Market<br />

<strong>Participant</strong>‟s Guide” document, which is available on <strong>IESO</strong>‟s web site (see the<br />

<strong>Technical</strong> Interfaces page of <strong>IESO</strong>‟s web site).<br />

3.2.5 Dispatch Message Scenarios<br />

219 Heart beat messages are sent by the <strong>IESO</strong> to determine whether the market<br />

participant is able to receive dispatch instructions from the <strong>IESO</strong>.<br />

<strong>IESO</strong> – Action MP –Response Comment<br />

HEARTOUT HEARTIN The <strong>IESO</strong> will send a HEARTOUT message<br />

every 60s to check for an active MP message<br />

exchange client. If the <strong>IESO</strong> does not receive<br />

the HEARTIN response from the client with a<br />

specified period of time (currently configured<br />

to 10s) the MP client is considered out of<br />

service and the Exchange Coordinator be<br />

informed of the problem.<br />