22 11 23-01-001 Patterson Split Case - Garney Construction
22 11 23-01-001 Patterson Split Case - Garney Construction
22 11 23-01-001 Patterson Split Case - Garney Construction
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
TEST REQUIREMENTS<br />
PATTERSON PUMP COMPANY<br />
PO BOX 790 2129 AYERSVILLE ROAD<br />
TOCCOA, GEORGIA 30577<br />
ORDER FIRST USED ON:<br />
SC-C<strong>01</strong>09398<br />
ISSUED BY: MS DATE: 12/14/<strong>11</strong> PAGE: 1 of 1<br />
TR-<strong>22</strong>41<br />
JOB: 254743 CUSTOMER ORDER NUMBER: 4383-<strong>22</strong><strong>11</strong><strong>23</strong>00<br />
S/N: C<strong>01</strong>09398 PUMP MODEL: 18x14MAB<br />
SUCTION DIAMETER: 18 DISCHARGE DIAMETER: 14 IMPELLER PATTERN: C-5762<br />
RATED POINT #1<br />
GPM: 6944<br />
HEAD: 179<br />
RPM: <strong>11</strong>80<br />
EFFICIENCY REQUIRED: 89%<br />
MAXIMUM BHP PERMISSIBLE: 400<br />
ROTATION:<br />
CW<br />
SUBMITTAL REQUIRED:<br />
X<br />
TEST ARRANGEMENT: Std. ASSEMBLY SECTION:<br />
NUMBER OF PUMPS TO BE TESTED: 3 GENERAL ARRANGEMENT: Std.<br />
WITNESS TEST: CERTIFIED TEST: X SHOP TEST: X FIELD TEST:<br />
X P.E. STAMP REQUIRED (give requirements to witness P.E.)<br />
TEST RANGE<br />
CAPACITY: Shut off GPM to Run out GPM<br />
HEAD: FT to FT<br />
SPEED: full RPM to full RPM<br />
POSITIVE SUCTION HEAD: SUCTION LIFT: X<br />
NUMBER OF TEST POINTS REQUIRED: 10 minim TEST POINT SPACING: std<br />
CURVE DATA REQUIRED<br />
H/Q: x SHUTOFF: x BHP/KW: x NPSH: PUMP EFFICIENCY: x<br />
OVERALL EFFICIENCY:<br />
x<br />
HYDROSTATIC PRESSURE: 135 PSI TIME: 10 min<br />
MOTOR(s) TO BE USED: JOB VOLTAGE: 460 HP: 400<br />
INDUCTION: X SYNCHRONOUS:<br />
MOTOR EFFICIENCY: COMPLETE TEST MOTOR COUPLING: JOB<br />
SPECIAL REQUIREMENTS<br />
1. See SPECS SECTION <strong>22</strong>-<strong>11</strong>-<strong>23</strong>.<strong>01</strong> /1.03 for other test requirements<br />
2. Submit test results for approval for all three pumps.<br />
3. Notify the Engineer starting date of the test.<br />
Form A04.10 9/28/95