ATTACHMENT B<br />
MOTOR SUBMITTAL DATA SHEET - HORIZONTAL CENTRIFUGAL PUMPING UNITS<br />
Submit the following data with shop drawing submittal for each size and type of Motor:<br />
Manufacturer<br />
Frame<br />
Type<br />
Voltage<br />
Starting Method<br />
Shaft Size<br />
Insulation Class<br />
SIEMENS<br />
50<strong>11</strong>S<br />
SQUIRREL CAGE<br />
460<br />
SOFT-START<br />
F-VPI<br />
Motor HP<br />
Enclosure<br />
RPM<br />
Phase<br />
Hertz<br />
Duty<br />
400<br />
TEFC<br />
<strong>11</strong>83<br />
3<br />
60<br />
CONTINUOUS<br />
Full Load Amps<br />
Locked Rotor Amps<br />
Locked Rotor Torque<br />
Locked Rotor kVA/HP<br />
487<br />
2807<br />
<strong>22</strong>91 lb-ft<br />
5.59<br />
No Load Amps<br />
Locked Rotor Torque<br />
% Breakdown Torque<br />
Rotor WK2 (lb-ft2)<br />
180.6<br />
129% FLT<br />
<strong>22</strong>6% FLT<br />
205<br />
NEMA Design<br />
Service Factor<br />
Inrush Current (% of Full Load)<br />
Number of Safe Starts Per Day<br />
-<br />
1.15<br />
576<br />
5,000 STARTS LIFETIME, FOLLOW GIVEN STARTING DUTY<br />
*Full Load Temp Rise, in Degree Celsius over 50 Celsius Ambient (at 1.0 S.F.)<br />
*Service Factor Temp Rise, in Degree Celsius over 50 Celsius Ambient (at 1.15 S.F.)<br />
80 DEG C BY DET<br />
90 DEG C BY DET<br />
*Limiting Temperature Rise<br />
Resistance (at 25 o C):<br />
Bearings: Type/Size<br />
0.00655 OHMS<br />
Life Lubrication:<br />
Exhaust Air (CFM) Exhaust Air Temp Rise ( o F)<br />
1.15 S.F. Load<br />
4/4 Load<br />
3/4 Load<br />
2/4 Load<br />
1/4 Load<br />
Efficiency Power Factor Current<br />
94.1 82.2 557<br />
94.4 81.4 487<br />
94.8 77.8 381<br />
94.5 68.7 288<br />
92.1 46.5 219<br />
RTD Types and Mounting<br />
RTD Alarm and Trip Set Point<br />
Motor Sound Power Level<br />
Motor Recommended Power Factor<br />
Space Heater Voltage<br />
STATOR: 100 OHM PLATINUM, EMBEDDED<br />
STATOR: ALARM = 155C, TRIP = 170C<br />
80dBA @ 3ft, UNLOADED<br />
FOR 95% PF: 1<strong>22</strong>kVAR<br />
120/240 Wattage<br />
525<br />
Horizontal Centrifugal Pumping Units <strong>22</strong> <strong>11</strong> <strong>23</strong>.<strong>01</strong>-20<br />
CMD<strong>11</strong>269 - Contract C-1 - Pumping Units and Motors<br />
10/06/<strong>11</strong>