8 Electrical<br />
The VORTEX Pro External module<br />
requires a 230/240 V ~ 50 Hz supply. It<br />
must be protected by a 5 Amp fuse.<br />
Refer to Figures 8-1 to 8-4 for typical<br />
control system wiring diagrams.<br />
Refer to Figure 8-5 for boiler internal<br />
wiring diagram.<br />
!<br />
WARNING<br />
The VORTEX Pro External module<br />
contains electrical switching<br />
equipment and must be earthed.<br />
The supply must be fused at 5 Amp<br />
and there must only be one common<br />
isolator for the boiler and control system,<br />
providing complete electrical isolation.<br />
A fused double pole switch or a<br />
fused three pin plug and shuttered<br />
outlet socket should be used for the<br />
connection.<br />
The power supply cable should be at<br />
least 0.75 mm² PVC as specified in BS<br />
6500, Table 16.<br />
All the wiring and supplementary earth<br />
bonding external to the boiler must be in<br />
accordance with the current I.E.E. Wiring<br />
Regulations.<br />
Any room thermostat or frost thermostat<br />
used must be suitable for use on mains<br />
voltage.<br />
The boiler requires a permanent mains<br />
supply, do not interrupt it with any<br />
external time control.<br />
In the event of an electrical fault after<br />
installation of the boiler, the following<br />
electrical system checks must be carried<br />
out:<br />
• Short circuit<br />
• Polarity<br />
• Earth continuity<br />
• Resistance to earth.<br />
8.1 Connecting the Power Supply<br />
!<br />
A Test switch is fitted to the control panel<br />
(see Figure 1-1) to allow the boiler to be<br />
test-fired. When On, the switch by-passes<br />
the external control system.<br />
It is recommend that the boiler should be<br />
connected to a switched mains power<br />
supply from a programmer or control<br />
system. If a <strong>Grant</strong> remote programmer is<br />
used, a permanent 240 V mains supply<br />
(fused at 5 Amp) must be taken to the<br />
boiler. A three core cable is required to<br />
connect the boiler terminal block to the<br />
live supply. Refer to Figures 8-1 to 8-4 for<br />
typical control system wiring diagrams.<br />
The procedure is:<br />
NOTE<br />
1. Undo the three screws and remove<br />
the lefthand cover from the control<br />
panel to gain access to the boiler<br />
terminal block.<br />
2. Pass the mains power supply<br />
cable through the cable grommet<br />
in the control panel, through the<br />
cable clamp and connect to the<br />
terminal block as follows:-<br />
Brown to live (terminal 2)<br />
Blue to mains neutral (terminal 3)<br />
Green/Yellow to mains earth<br />
(terminal 4)<br />
3. Refer to Figures 8-1 to 8-4 for<br />
a typical control system wiring<br />
diagrams.<br />
4. If the circulating pump is to be<br />
fitted within the boiler enclosure,<br />
the pump live must be connected<br />
to terminal 7 of the boiler terminal<br />
block.<br />
Pass the pump power supply<br />
cable through the cable grommet<br />
in the control panel, through the<br />
cable clamp and connect to the<br />
terminal block as follows:-<br />
Brown to live (terminal 7)<br />
Blue to mains neutral (terminal 9)<br />
Green/Yellow to earth (terminal<br />
Connecting the pump in this way<br />
allows it to be isolated using the<br />
isolating switch fitted in the boiler<br />
control panel, for servicing or<br />
maintenance work.<br />
5. Ensure that the cable clamp is<br />
tightened and that all cables are<br />
secure and all external wiring is<br />
adequately supported.<br />
6. Replace the cover on the control<br />
panel, with the yellow warning<br />
label facing outwards and secure<br />
with the three screws.<br />
Do not switch on the electricity supply<br />
to the External module at this stage.<br />
8.2 Frost Protection<br />
External Modules are supplied with<br />
a factory fitted frost protection<br />
thermostat, located inside the boiler<br />
control panel. This is pre-wired to the<br />
boiler electrical system and factory set<br />
to 2°C.<br />
For total system protection against<br />
freezing, particularly during extended<br />
periods without electrical power,<br />
<strong>Grant</strong> recommend the use of a<br />
combined heating system antifreeze<br />
and corrosion inhibitor, used in<br />
accordance with the manufacturer's<br />
instructions.<br />
Electrical<br />
23