16.11.2014 Views

Installation & Servicing Instructions - Grant UK

Installation & Servicing Instructions - Grant UK

Installation & Servicing Instructions - Grant UK

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

9 Flue System and Air Supply<br />

9.1 Low Level Discharge Flue<br />

The <strong>Grant</strong> VORTEX Pro External module<br />

is supplied with a low level discharge flue<br />

(see Section 4).<br />

The minimum dimensions for locating the<br />

standard terminal from building features<br />

(windows, doors, etc.) are shown in<br />

Figure 9-1.<br />

The terminal must be positioned so<br />

as to avoid products of combustion<br />

accumulating in stagnant pockets<br />

around the buildings or entering into<br />

buildings. Care should be taken that the<br />

plume from the condensed flue gases<br />

does not cause a nuisance.<br />

Where it is not practical to use this flue,<br />

the External module may be fitted with<br />

an alternative flue system available from<br />

<strong>Grant</strong> <strong>UK</strong>.<br />

!<br />

NOTE<br />

Under no circumstances can the<br />

External module be installed with an<br />

existing flue system. Only <strong>Grant</strong> flue<br />

systems and components suitable for<br />

wet flues should be used.<br />

Failure to install the correct type<br />

of flue system will invalidate the<br />

warranty.<br />

9.2 <strong>Grant</strong> Green System<br />

This vertical twin wall stainless steel<br />

insulated flue system - constructed<br />

using components from the <strong>Grant</strong> Green<br />

system - connects to a <strong>Grant</strong> Starter<br />

elbow and may terminate at high level or<br />

vertically as required. See Figure 9-2.<br />

The insulated Starter elbow includes<br />

the boiler connector, complete with test<br />

point, replacing the low level terminal<br />

and flue guard supplied with the boiler.<br />

Figure 9-1: Clearances for flue terminals<br />

Terminal position<br />

A Below a gutter or sanitary pipework<br />

B Horizontal from an opening, air brick or window<br />

C Above ground or balcony level<br />

D Below eaves or balcony<br />

E From an internal or external corner<br />

F From a terminal facing the terminal<br />

G From a surface facing the terminal<br />

H Vertical from terminals on the same wall<br />

I Horizontal from terminals on the same wall<br />

J Below an opening, air brick, window etc.<br />

K From vertical sanitary pipework<br />

From an oil storage tank<br />

Notes:<br />

* 75 mm with protection.<br />

** Only applies if one or both terminals are balanced flues.<br />

Min. distance (mm)<br />

600 *<br />

600<br />

300<br />

600 *<br />

300<br />

1200<br />

600<br />

1500<br />

750 **<br />

600<br />

300<br />

1800<br />

The terminal should be positioned so as to avoid products of combustion accumulating<br />

in stagnant pockets around the building or entering into buildings. Care should also be<br />

taken that the plume from the condensed flue gases does not cause a nuisance.<br />

Distances measured to rim of terminal.<br />

Clearances recommended by <strong>Grant</strong> <strong>UK</strong><br />

in accordance with British Standards<br />

and Building Regulations.<br />

!<br />

NOTE<br />

1. An opening means an openable<br />

element, such as an openable<br />

window, or a permanent opening<br />

such as a permanently open air vent.<br />

2. Notwithstanding the dimensions<br />

given, a terminal should be at<br />

least 300 mm from combustible<br />

material, e.g. a window frame.<br />

3. A way of providing protection of<br />

combustible material would be to fit<br />

a heat shield at least 750 mm wide.<br />

Flue System<br />

27

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!