<strong>USDT</strong> <strong>3004</strong><br />
System layout 3<br />
The controller calculates the temperature difference between<br />
collector sensor S1 and tank sensor S2. If the difference<br />
is larger than or identical to the adjusted switch-on<br />
temperature difference (DT O), the solar pump will be<br />
operated by relay 1, and the tank will be loaded until the<br />
switch-off temperature difference (DT F) or the maximum<br />
tank temperature (S MX) is reached.<br />
If the maximum collector temperature (CMX) is reached, the<br />
solar pump will be operated by relay 1 and the 3-way-valve<br />
will be operated by relay 2 in order to direct the surplus<br />
energy to a heat dump. For security purpose this will be<br />
carried out only if the tank temperature is below the nonadjustable<br />
emergency shutdown of 200 °F.<br />
Sensors S3 and S4 can optionally be connected for measurement<br />
purposes.<br />
If energy metering (OHQM) is activated, sensor S4 has to<br />
be connected as return sensor.<br />
Arr 3<br />
VBus<br />
10 9<br />
S1<br />
R2<br />
R1<br />
S3<br />
S4 / TR<br />
S2<br />
Display Channels<br />
Channel Description Terminal Page<br />
COL x Temperature collector S1 18<br />
TST x Temperature tank S2 18<br />
S3 x Temperature sensor 3 S3 18<br />
S4 x Temperature sensor 4 S4 18<br />
TR x* Temperature return sensor S4 18<br />
n % x Pump speed relay R1 18<br />
h P1 x Operating hours R1 R1 19<br />
h P2 x Operating hours R2 R2 19<br />
kWh x* Heat quantity kWh - 19<br />
MWh x* Heat quantity MWh - 19<br />
TIME x Time - 16<br />