<strong>USDT</strong> <strong>3004</strong><br />

4.2 Adjustment channels<br />

System layout selection<br />

Arr:<br />

System layout selection.<br />

Adjustment range: 1 ... 3<br />

Factory setting: 1<br />

Security enquiry:<br />

In this channel, a pre-defined system layout can be selected.<br />

Each system layout has a set of pre-programmed settings<br />

that can be individually changed.<br />

If the system layout selection is changed later on, all adjustments<br />

made in the other channels will be lost. Therefore,<br />

changing the system layout is always followed by a security<br />

enquiry.<br />

Only confirm the security enquiry if you are sure that<br />

you wish to change the system layout selection!<br />

ÎÎTo confirm the security enquiry, press button 3<br />

∆T-regulation<br />

DT O:<br />

Switch-on temperature diff.<br />

Adjustment range: 2.0 ... 40.0°Ra<br />

[1.0 ... 20.0 K]<br />

in steps of 1 °Ra [0.5 K]<br />

Factory setting: 12.0°Ra<br />

[6.0 K]<br />

DT F:<br />

Switch-off temperature diff.<br />

Adjustment range: 1.0 ... 39.0°Ra<br />

[0.5 ... 19.5 K]<br />

in steps of 1 °Ra [0.5 K]<br />

Factory setting: 8.0°Ra<br />

[4.0 K]<br />

Pump speed control<br />

DT S:<br />

Nominal temperature difference<br />

Adjustment range: 3.0 ... 60.0 °Ra<br />

[1.5 ... 30.0 K]<br />

in steps of 1 °Ra [0.5 K]<br />

Factory setting: 20.0 °Ra<br />

[10.0 K]<br />

RIS:<br />

Rise<br />

Adjustment range:<br />

2 ... 40 °Ra [1 ... 20 K]<br />

in steps of 2 °Ra [1 K]<br />

Factory setting: 4 °Ra [2 K]<br />

Minimum pump speed<br />

nMN:<br />

Pump speed control<br />

Adjustment range:<br />

30 ... 100<br />

in steps of 5 %<br />

Factory setting: 30<br />

| 20<br />

The controller works as a standard differential controller. If<br />

the switch-on difference is reached, the pump is activated.<br />

When the temperature difference falls below the adjusted<br />

switch-off temperature difference, the relay switches off.<br />

Note:<br />

The switch-on temperature difference must be<br />

at least 1 °Ra [0.5 K] higher than the switch-off<br />

tempe rature difference.<br />

Note:<br />

When the drainback option ODB is activated,<br />

the temperature differences DT O, DT F and<br />

DT S are set to a fixed adjustment:<br />

DT O = 20 °Ra [10 K]<br />

DT F = 8 °Ra [4 K]<br />

DT S = 30 °Ra [15 K]<br />

Previous adjustments made in these channels will<br />

be overridden and may have to be entered again if<br />

ODB is deactivated later on.<br />

Note:<br />

For pump speed control, the operation mode of<br />

relay 1 must be set to Auto (adjustment channel<br />

MAN1)<br />

When the switch-on temperature difference is reached,<br />

the pump is activated at full speed for 10 seconds. Then, the<br />

speed is reduced to the minimum pump speed value (factory<br />

setting = 30 %).<br />

If the temperature difference reaches the adjusted nominal<br />

temperature difference, the pump speed increases by one<br />

step (10 %). If the difference increases by the adjustable rise<br />

value, the pump speed increases by 10 % respectively until the<br />

maximum pump speed of 100 % is reached. The response of<br />

the controller can be adapted via the parameter “Rise”.<br />

Note:<br />

The nominal temperature difference must be<br />

at least 1 °Ra [0.5 K] higher than the switch-on<br />

tempe rature difference.<br />

A relative minimum pump speed can be allocated to the<br />

output R1 via the adjustment channel nMN.<br />

Note:<br />

When a load which is not speed-controlled is<br />

used, the value must be set to 100 % in order to<br />

deactivate pump speed control.<br />

© 10259_usdt_<strong>3004</strong>.monus.indd