<strong>SMA</strong> Solar Technology AG<br />

Electrical Connection<br />

NOTICE!<br />

Excessive currents can damage the inverter!<br />

• The maximum current per DC connector plug may not exceed 16 A.<br />

DANGER!<br />

Risk of lethal electric shock!<br />

• Do not connect strings with ground faults.<br />

• First, rectify the ground fault in the respective string.<br />

5. Check the DC plug connectors for correct polarity and connect them.<br />

To release the DC plug connectors, see section 7.2 ”Opening the Inverter” (page 37).<br />

6. To create the sealing on the inverter, all the DC<br />

inputs have to be closed as follows:<br />

– Insert the sealing plugs provided into the DC<br />

plug connectors that are not required.<br />

Do not insert the sealing plugs into the DC<br />

inputs on the inverter.<br />

– Insert the DC plug connectors with sealing plugs<br />

into the corresponding DC inputs on the inverter.<br />