Electrical Connection<br />
NOTICE!<br />
Excessive currents can damage the inverter!<br />
• The maximum current per DC connector plug may not exceed 16 A.<br />
DANGER!<br />
Risk of lethal electric shock!<br />
• Do not connect strings with ground faults.<br />
• First, rectify the ground fault in the respective string.<br />
5. Check the DC plug connectors for correct polarity and connect them.<br />
To release the DC plug connectors, see section 7.2 ”Opening the Inverter” (page 37).<br />
6. To create the sealing on the inverter, all the DC<br />
inputs have to be closed as follows:<br />
– Insert the sealing plugs provided into the DC<br />
plug connectors that are not required.<br />
Do not insert the sealing plugs into the DC<br />
inputs on the inverter.<br />
– Insert the DC plug connectors with sealing plugs<br />
into the corresponding DC inputs on the inverter.<br />
Installation Guide SB33_38-IEN100540 33