Troubleshooting<br />

Message<br />

VpvMax<br />

Watchdog<br />

Watchdog Srr<br />

Zac-Bfr<br />

Zac-Srr<br />

Description and corrective measure<br />

Overvoltage at DC input. The inverter may be damaged.<br />

Corrective measures<br />

Disconnect the inverter from the grid immediately.<br />

1. Turn off the line circuit breaker.<br />

2. Remove the Electronic Solar Switch.<br />

3. Disconnect all the DC plug connectors.<br />

4. Check DC voltage:<br />

– If the DC voltage is above the maximum input voltage, check the<br />

system design or contact the installer of the PV generator.<br />

– If the DC voltage is under the maximum input voltage, reconnect<br />

the inverter to the PV generator as described in section<br />

5.5 ”Connection of the PV Generator (DC)” (page 28).<br />

If the message occurs again, disconnect the inverter again and contact<br />

the <strong>SMA</strong> Serviceline (see section 13 ”Contact” (page 66)).<br />

Internal program run fault.<br />

Corrective measures<br />

• Contact the <strong>SMA</strong> Serviceline if this disturbance occurs frequently.<br />

The grid impedance is no longer within the permissible range ("Bfr" or<br />

"Srr" is an internal message of no relevance for the user). For safety<br />

reasons, the inverter disconnects itself from the grid. The impedance is<br />

calculated from both the grid impedance and the impedance of the AC<br />

cable of the inverter.<br />

Corrective measures<br />

• Check the grid impedance and grid connection on the inverter.<br />

• Use an AC cable with an adequate cross-sectional area<br />

(= low impedance) as described in section 5.3 ”Connection to the<br />

Public Grid (AC)” (page 22). If required, check and re-tighten the<br />

screws on the AC terminals.<br />

• If this fault recurs, please contact the <strong>SMA</strong> Serviceline.<br />

Installation Guide SB33_38-IEN100540 51