<strong>SMA</strong> Solar Technology AG<br />
Opening and Closing<br />
7 Opening and Closing<br />
7.1 Safety<br />
DANGER!<br />
Risk of lethal electric shock!<br />
Pay attention to the following points before opening the inverter:<br />
• Ensure that there are no hazardous voltages present on the AC side.<br />
• Ensure that there are no hazardous currents or voltages present on the DC side.<br />
NOTICE!<br />
Static discharges can damage the inverter!<br />
Internal components of the inverter can be irreparably damaged by electrostatic<br />
discharge.<br />
• Ground yourself before touching a component.<br />
7.2 Opening the Inverter<br />
1. Disconnect the line circuit breaker and secure it to prevent it from being reactivated.<br />
2. Pull the Electronic Solar Switch downward, slightly<br />
toward the wall.<br />
3. Using a current probe, ensure that there is no<br />
current to all DC cables.<br />
☑ If current is detected, check the installation!<br />
Installation Guide SB33_38-IEN100540 37