<strong>SMA</strong> Solar Technology AG<br />

Troubleshooting<br />

Message<br />

Imax<br />

K1-Close<br />

K1-Open<br />

MSD-Fac<br />

MSD-Vac<br />

NUW-Timeout<br />

MSD-Timeout<br />

Offset<br />

Riso<br />

ROM<br />

Description and corrective measure<br />

Overcurrent on the AC side. This fault code is displayed if the current in<br />

the AC grid is larger than specified.<br />

Corrective measures<br />

• Check the system design and grid conditions.<br />

Fault during relay test.<br />

Corrective measures<br />

• Contact the <strong>SMA</strong> Serviceline if this problem occurs frequently or<br />

several times in succession.<br />

Internal measurement comparison fault or hardware defect.<br />

Corrective measures<br />

• Contact the <strong>SMA</strong> Serviceline if this disturbance occurs frequently.<br />

Internal measurement comparison fault or hardware defect.<br />

Corrective measures<br />

• Contact the <strong>SMA</strong> Serviceline if this disturbance occurs frequently.<br />

Internal measurement comparison fault or hardware defect.<br />

Corrective measures<br />

• Contact the <strong>SMA</strong> Serviceline if this disturbance occurs frequently.<br />

Internal measurement comparison fault or hardware defect.<br />

Corrective measures<br />

• Contact the <strong>SMA</strong> Serviceline if this disturbance occurs frequently.<br />

The "Derating" operating condition is a normal operating condition that<br />

occurs prior to grid monitoring.<br />

If "offset" is displayed as an error, then there is a disturbance in the data<br />

logging.<br />

Corrective measures<br />

• Contact the <strong>SMA</strong> Serviceline if this disturbance occurs frequently.<br />

The electrical insulation between the PV system and ground is faulty. The<br />

resistance between the DC plus and/or DC minus connection and ground<br />

is outside the defined limit range.<br />

Corrective measures<br />

• Check the insulation of the system.<br />

• Check the system for ground faults as described in section<br />

9.3.1 ”Checking the PV Generator for a Ground Fault” (page 52).<br />

The inverter's firmware is faulty.<br />

Corrective measures<br />

• Contact the <strong>SMA</strong> Serviceline if this disturbance occurs frequently.<br />

Installation Guide SB33_38-IEN100540 49