Troubleshooting<br />
Message<br />
Imax<br />
K1-Close<br />
K1-Open<br />
MSD-Fac<br />
MSD-Vac<br />
NUW-Timeout<br />
MSD-Timeout<br />
Offset<br />
Riso<br />
ROM<br />
Description and corrective measure<br />
Overcurrent on the AC side. This fault code is displayed if the current in<br />
the AC grid is larger than specified.<br />
Corrective measures<br />
• Check the system design and grid conditions.<br />
Fault during relay test.<br />
Corrective measures<br />
• Contact the <strong>SMA</strong> Serviceline if this problem occurs frequently or<br />
several times in succession.<br />
Internal measurement comparison fault or hardware defect.<br />
Corrective measures<br />
• Contact the <strong>SMA</strong> Serviceline if this disturbance occurs frequently.<br />
Internal measurement comparison fault or hardware defect.<br />
Corrective measures<br />
• Contact the <strong>SMA</strong> Serviceline if this disturbance occurs frequently.<br />
Internal measurement comparison fault or hardware defect.<br />
Corrective measures<br />
• Contact the <strong>SMA</strong> Serviceline if this disturbance occurs frequently.<br />
Internal measurement comparison fault or hardware defect.<br />
Corrective measures<br />
• Contact the <strong>SMA</strong> Serviceline if this disturbance occurs frequently.<br />
The "Derating" operating condition is a normal operating condition that<br />
occurs prior to grid monitoring.<br />
If "offset" is displayed as an error, then there is a disturbance in the data<br />
logging.<br />
Corrective measures<br />
• Contact the <strong>SMA</strong> Serviceline if this disturbance occurs frequently.<br />
The electrical insulation between the PV system and ground is faulty. The<br />
resistance between the DC plus and/or DC minus connection and ground<br />
is outside the defined limit range.<br />
Corrective measures<br />
• Check the insulation of the system.<br />
• Check the system for ground faults as described in section<br />
9.3.1 ”Checking the PV Generator for a Ground Fault” (page 52).<br />
The inverter's firmware is faulty.<br />
Corrective measures<br />
• Contact the <strong>SMA</strong> Serviceline if this disturbance occurs frequently.<br />