Frame [14]<br />
The frame is constructed from steel profile sections. Vibration absorption dampers are supplied<br />
separately and must be fitted after the unit has been placed in position.<br />
The casing [27]<br />
The casing consists of panels that can be removed easily without the aid of tools.<br />
The electrical section<br />
This includes the control and safety circuits for the unit.<br />
Connection box [25]<br />
The electrical power supply for the boiler, the terminals, the pump connections and the pump<br />
relay are mounted in an easily accessible connection box. The supply cables can easily be fed to<br />
the connection box via the cable duct inside the boiler [21].<br />
2.3 Boiler control<br />
The principle employed for the Boiler Management Unit is as follows: The boiler begins operating<br />
on receipt of a heating demand. This heating demand is generated either:<br />
A. If the measured supply temperature is lower than the desired temperature.<br />
B. As a result of “manual operation” mode having been se lected (W1 or W2),<br />
C. in standby mode, when the water temperature falls below the frost protection temperature.<br />
After the unit has started up, the PID controller sends a signal to the frequency converter. This<br />
converter controls the speed of the fan. Depending on the quantity of air moved by the fan, the<br />
proportional pressure regulator ensures that the corresponding quantity of gas is added.<br />
In this way the boiler capacity is continually adjusted and the boiler can accurately follow the<br />
heating demand. If the boiler is operating at minimum capacity and the temperature of the supply<br />
water rises above the desired value, the unit will be shut down. As soon as the temperature of the<br />
supply water falls below the set value, the boiler will be re-started.<br />
2.4 Safety aspects<br />
The unit contains the following safety components:<br />
- Flame protection on pilot and main burner (1x re-start)<br />
- Water flow protection<br />
- Maximum water temperature protection<br />
- Gas valve test<br />
- Fan protection<br />
- Boiler pump motor over-heating protection.<br />
If one of these components operates, this results in a lockout fault. Lockout faults can only be<br />
cancelled by resetting the unit.<br />
The unit is fitted with a safety valve that opens at 3 bar.