Frame [14]<br />

The frame is constructed from steel profile sections. Vibration absorption dampers are supplied<br />

separately and must be fitted after the unit has been placed in position.<br />

The casing [27]<br />

The casing consists of panels that can be removed easily without the aid of tools.<br />

The electrical section<br />

This includes the control and safety circuits for the unit.<br />

Connection box [25]<br />

The electrical power supply for the boiler, the terminals, the pump connections and the pump<br />

relay are mounted in an easily accessible connection box. The supply cables can easily be fed to<br />

the connection box via the cable duct inside the boiler [21].<br />

2.3 Boiler control<br />

The principle employed for the Boiler Management Unit is as follows: The boiler begins operating<br />

on receipt of a heating demand. This heating demand is generated either:<br />

A. If the measured supply temperature is lower than the desired temperature.<br />

B. As a result of “manual operation” mode having been se lected (W1 or W2),<br />

C. in standby mode, when the water temperature falls below the frost protection temperature.<br />

After the unit has started up, the PID controller sends a signal to the frequency converter. This<br />

converter controls the speed of the fan. Depending on the quantity of air moved by the fan, the<br />

proportional pressure regulator ensures that the corresponding quantity of gas is added.<br />

In this way the boiler capacity is continually adjusted and the boiler can accurately follow the<br />

heating demand. If the boiler is operating at minimum capacity and the temperature of the supply<br />

water rises above the desired value, the unit will be shut down. As soon as the temperature of the<br />

supply water falls below the set value, the boiler will be re-started.<br />

2.4 Safety aspects<br />

The unit contains the following safety components:<br />

- Flame protection on pilot and main burner (1x re-start)<br />

- Water flow protection<br />

- Maximum water temperature protection<br />

- Gas valve test<br />

- Fan protection<br />

- Boiler pump motor over-heating protection.<br />

If one of these components operates, this results in a lockout fault. Lockout faults can only be<br />

cancelled by resetting the unit.<br />

The unit is fitted with a safety valve that opens at 3 bar.