8.5 Cleaning the filter/screen in the gas combination block<br />
Not applicable<br />
8.6 Ionisation measurement<br />
In order to carry out an ionisation measurement, a micro-am meter with a measuring range of<br />
0 - 200 µA DC must be con nected in the ionisation circuit. In this way the ionisation protec tion<br />
function can be checked. The nominal ionisation current is between 6 and 25 µA. The minimum<br />
ionisation current is 2.8 µA.<br />
8.7 Service<br />
For service and maintenance the service department of your supplier is always available.<br />
9 Conversion formulae and factors<br />
Formulae<br />
CO<br />
2<br />
20.<br />
9 − measured O<br />
=<br />
20.9<br />
2<br />
× 11.<br />
7<br />
measured CO × 20.<br />
9<br />
O 2 = 20.<br />
9 −<br />
2<br />
11.<br />
7<br />
11.7% CO 2 is the maximum CO 2 percentage that is generated by stoichiometric burning of G20<br />
natural gas (H-gas).<br />
Excess air N:<br />
20.<br />
9<br />
N =<br />
20. 9 − m easured O 2<br />
× 0.<br />
914<br />
or<br />
N = 1 ⎛ 11.<br />
7 ⎞<br />
+ ⎜<br />
− 1⎟ ⎝ m ⎠<br />
× 0.<br />
914<br />
CO easured<br />
2<br />
Conversion factors<br />
For NO x (N=1):<br />
1 ppm = 2.05 mg/m 3 = 1.759 mg/kWh = 0.498 mg/MJ<br />
For CO (N=1):<br />
1 ppm = 1.24 mg/m 3 = 1.064 mg/kWh = 0.298 mg/MJ<br />
Example:<br />
Measured values for an environmentally friendly unit:<br />
NO x = 15 ppm<br />
CO 2 = 10 %<br />
What is the value for NO x according to the most usual standard in mg/kWh for N=1<br />
10 × 20.<br />
9<br />
O 2 = 20.<br />
9 − = 3%<br />
11.<br />
7<br />
52 Doc890/3456CV02B