Operating mode (cover closed)<br />

With the cover closed and by using the rotational switch (pos. No. 2) clockwise or anti-clockwise<br />

the boilers’ operating mode can be set.<br />

The operating modes are:<br />

K standby the boiler switched off but frost protection is active<br />

F automatic the boiler can operate in heating or direct hot water mode<br />

t summer mode the boiler will only react to a direct hot water demand<br />

W1 manual, low capacity the boiler will run at low capacity<br />

W2 manual, high capacity the boiler will run at full capacity<br />

Information mode<br />

With the cover open and by turning the rotational switch (Pos. No 5) clockwise or anti-clockwise it<br />

is possible to read out certain information from the boiler management unit.<br />

There are 10 possibilities. An arrow at the bottom of the LCD display will indicate which parameter<br />

has been selected. The following parameters are readable:-<br />

Parameter<br />

P1 actual flow temperature<br />

P2 actual direct hot water temperature (if used)<br />

P3 setpoint temperature<br />

P5 actual outside temperature (if used)<br />

P8 temperature at the low velocity header (if used)<br />

P9 actual boiler capacity<br />

P10 only for trained service engineers<br />

Summary of input and output indications (cover open)<br />

Input indications:<br />

H Flame Ionisation detected<br />

SW Water flow switch in operating position<br />

DW APS in operating position<br />

RT Boiler enabled by BMS<br />

Bus Data-bus detected<br />

Output indications:<br />

r Power to Main Gas Valve<br />

u Power to Ignitor<br />

s Control signal to fan<br />

Z Power to Primary Boiler Pump<br />

t Power to Primary DHW Pump<br />

Setting the flow temperature for Central Heating (cover open)<br />

Only applicable to boilers without weather compensated flow temperature or a 0-10 Volt control<br />

signal.<br />

N.B. Only applicable if outside temperature compensation or a 0-10 V signal is not used.<br />

- Open the lid (the arrow at the bottom of the LCD display indicates parameter P1)<br />

- Press the combined Reset/Programming key (pos. 3). The LED will light. Turn the rotary switch<br />

(pos.5) until the desired water flow temperature has been reached<br />

- Press the combined Reset/Programming key. The LED will go out<br />

- Close the cover.<br />

N.B. The new temperature setting will only become active once the Reset/Programming key has<br />

been released.<br />