<strong>Rendamax</strong><br />

The gas connection is made at the rear of the boiler.<br />

Types R3401, R3402, the R3501 - R3505 and R3601 - R3605 are not suitable for immediate connection<br />

to a 100 mbar natural gas system (as option 100 mbar). The pressure of the gas sup-plied to<br />

the unit must be reduced to 25 mbar for natural gas or 50 mbar for propane with the use of a gas<br />

pressure regulator.<br />

From type R3403, all boilers are suitable for gas supply pres sures of 100 mbar on natural gas.<br />

The loss of pressure in the connecting pipes must be such that, at maximum boiler capacity, the<br />

pressure must never fall below 18 mbar for natural gas or 50 mbar for propane.<br />

5.3.2 Electrical connection<br />

The electrical connections and provisions must comply with the applicable national and local<br />

standards and regulations.<br />

The units are wired in accordance with the electrical diagram supplied with the appliance.<br />

w<br />

The electrical connections, the terminals and the boiler pump relay are mounted in a separate<br />

connection box behind the front panel (extrusion profile, fig. 4).<br />

This front panel can be simply removed by pulling the lower edge of the panel forward. Behind<br />

this panel are two cover plates which can be removed by unscrewing the M5 bolts. The terminal<br />

strip with the connection clamps are mounted behind the lower cover plate.<br />

The cables to be connected (power supply, control) enter the appliance via the rear of the unit,<br />

and pass via the cable duct at the inner right hand side to the connection box at the front of the<br />

unit. The connection box is provided with cable glands and connection terminals. The boiler pump<br />

is provided with thermal protection and a pump relay.<br />

control panel<br />

transformer 230-24-25V<br />

CXE/EM<br />

mains filter<br />

frequency converter<br />

terminal strip with<br />

terminal functions<br />

cable glands<br />

boiler pump relay<br />

Fig. 16<br />

Connection box<br />

The appliance can be switched on and off with the switch on the control panel. The power supply<br />

voltage cannot be removed from the boiler pump relay in this way.<br />

x<br />

The installer must fit a mains isolator switch in the power supply to the unit within the boiler<br />

room. This can be used to switch off the power to the unit for maintenance purposes or in the<br />

event of a problem.<br />

26 Doc890/3456CV02B