<strong>Rendamax</strong><br />

Type<br />

UPS 65-120F<br />

R3401 - R3403<br />

R3501 - R3503<br />

R3601 - R3603<br />

UPS 80-120F<br />

R3404 - R3405<br />

R3504 - R3505<br />

R3604 - R3605<br />

Pump<br />

speed<br />

1<br />

2<br />

3<br />

1<br />

2<br />

3<br />

Pmax<br />

W<br />

850<br />

900<br />

1150<br />

1000<br />

1100<br />

1500<br />

Pmin<br />

W<br />

440<br />

460<br />

600<br />

710<br />

760<br />

960<br />

I<br />

A<br />

3x400 V<br />

1.35<br />

1.45<br />

2.15<br />

1.65<br />

1.80<br />

2.75<br />

cos<br />

φ<br />

0.91<br />

0.90<br />

0.77<br />

0.87<br />

0.88<br />

0.79<br />

LM 80-160/162<br />

R3406 - 1500 - 4.05 0.79-0.70<br />

Table 13<br />

Electrical <strong>data</strong> for pumps<br />

5.4.2.3 Isolating valves<br />

It is recommended that manual valves be fitted between the flow and return connections and the<br />

installation.<br />

5.4.2.4 Valves<br />

For <strong>R3400</strong>/R3500/R3600 units connected in cascade, a de layed motorised shut-off valve can be<br />

used if it is controlled by the boiler using terminals 14 + 15 or alternatively, a mechanical non-return<br />

valve can be used. This is required so as to avoid short-circuiting the appliance on the water<br />

side.<br />

5.4.2.5 Water flow protection<br />

The unit is provided with water flow protection. This shuts the appliance down in the event that<br />

the flow of water through the appliance falls below the minimum required value. This protec tion is<br />

implemented by means of a water flow switch.<br />

5.4.3 Water pressure<br />

5.4.3.1 Operating pressure<br />

At a maximum supply temperature of 90°C and a minimum water flow rate such as occurs at a ∆T<br />

y<br />

of 20 K, the minimum operating pressure must be greater than 1.5 bar. The operating pressure<br />

must be measured with the pump switched off. If a lower pressure is desired, the maximum supply<br />

temperature must be adjusted accordingly.<br />

Minimum operating<br />

pressure in bar<br />

›1.5<br />

›1<br />

Flow temperature<br />

°C<br />

90<br />

80<br />

∆T<br />

K<br />

20<br />

20<br />

Table 14<br />

minimum operating pressures<br />

5.4.3.2 Boiler expansion tank<br />

It is advisable to fit an expansion tank in the return pipe be tween pump and the boiler isolating<br />

valve.<br />

5.4.3.3 System expansion tank<br />

The size of the expansion tank is determined by the quantity of water in the system. Our advice is<br />

to fit the system expansion tank at the neutral point (centrally) of the low velocity header.<br />

5.4.3.4 Water pressure protection<br />

All appliances are fitted with a safety valve that opens at 3 bar. As an option, safety valves can be<br />

supplied with settings be tween 3 and 6 bar with increments of 1 bar.<br />