In order to limit the losses occurring in a non-operational boiler, a motorised valve is sometimes<br />

fitted in the flow or the return pipe or a mechanical non-return valve is used for this purpose.<br />

Standby losses can be reduced even further by shutting down the boiler via the “boiler enable”<br />

terminals. A properly dimension ed low velocity header ensures that the natural flow through the<br />

boiler can be neglected.<br />

5.3.4 Combustion air supply<br />

5.3.4.1 General<br />

The unit can optionally be supplied as a room sealed appli ance. This simplifies the possibilities<br />

for installation within the building.<br />

Guide lines and installation instructions<br />

The flue gas discharge and the air supply systems must be installed by a recognised installer in<br />

accordance with the appli cable national and local specifications and regulations.<br />

The total resistance of the air supply and the flue may not result in a pressure drop exceeding 1.5<br />

mbar.<br />

If the unit is used as a room sealed appliance, open Tees or draught stabiliser are not permitted.<br />

5.3.4.2 Air supply pipe<br />

The air supply pipe may be single-walled and constructed of:<br />

- plastic<br />

- thin-walled aluminium<br />

- flexible aluminium (take account of the resistance).<br />

Fig. 18<br />

Horizontal air supply<br />

Type<br />

Air supply<br />

diameter (mm)<br />

X<br />

(mm)<br />

Y<br />

(mm)<br />

D1<br />

D2<br />

R3401<br />

R3402<br />

R3403<br />

R3404<br />

R3405<br />

R3406<br />

R3501<br />

R3502<br />

R3503<br />

R3504<br />

R3505<br />

R3601<br />

R3602<br />

R3603<br />

R3604<br />

R3605<br />

250<br />

300<br />

300<br />

300<br />

355<br />

355<br />

355<br />

239.5<br />

239.5<br />

289.5<br />

239.5<br />

239.5<br />

289.5<br />

233.5<br />

359<br />

359<br />

266<br />

266<br />

266<br />

266<br />

266<br />

Table 8<br />

Air supply connection<br />

30 Doc890/3456CV02B