In order to limit the losses occurring in a non-operational boiler, a motorised valve is sometimes<br />
fitted in the flow or the return pipe or a mechanical non-return valve is used for this purpose.<br />
Standby losses can be reduced even further by shutting down the boiler via the “boiler enable”<br />
terminals. A properly dimension ed low velocity header ensures that the natural flow through the<br />
boiler can be neglected.<br />
5.3.4 Combustion air supply<br />
5.3.4.1 General<br />
The unit can optionally be supplied as a room sealed appli ance. This simplifies the possibilities<br />
for installation within the building.<br />
Guide lines and installation instructions<br />
The flue gas discharge and the air supply systems must be installed by a recognised installer in<br />
accordance with the appli cable national and local specifications and regulations.<br />
The total resistance of the air supply and the flue may not result in a pressure drop exceeding 1.5<br />
mbar.<br />
If the unit is used as a room sealed appliance, open Tees or draught stabiliser are not permitted.<br />
5.3.4.2 Air supply pipe<br />
The air supply pipe may be single-walled and constructed of:<br />
- plastic<br />
- thin-walled aluminium<br />
- flexible aluminium (take account of the resistance).<br />
Fig. 18<br />
Horizontal air supply<br />
Type<br />
Air supply<br />
diameter (mm)<br />
X<br />
(mm)<br />
Y<br />
(mm)<br />
D1<br />
D2<br />
R3401<br />
R3402<br />
R3403<br />
R3404<br />
R3405<br />
R3406<br />
R3501<br />
R3502<br />
R3503<br />
R3504<br />
R3505<br />
R3601<br />
R3602<br />
R3603<br />
R3604<br />
R3605<br />
250<br />
300<br />
300<br />
300<br />
355<br />
355<br />
355<br />
239.5<br />
239.5<br />
289.5<br />
239.5<br />
239.5<br />
289.5<br />
233.5<br />
359<br />
359<br />
266<br />
266<br />
266<br />
266<br />
266<br />
Table 8<br />
Air supply connection<br />
30 Doc890/3456CV02B