2-3 Initial Wiring Confidence Check<br />
2-3A Input 3-phase Wiring<br />
The wiring of the individual phases of input power to the controllers does not make any<br />
difference in the behavior of the drive motors. Guarantee that 208/440 or 470 three phase 60 Hz<br />
power is available.<br />
2-3B Output 3-phase Wiring<br />
The wiring of phases between the controller and the motor affects the direction of motor<br />
movement Reverse any two (2) phases of the controllers output to the motor, in order to reverse<br />
the motor direction. Perform paragraph 2-4<br />
To test and set correct drive rotation of all motors. Output power is digital DC to the drive<br />
motors.<br />
2-4 MANUAL CONTROL OF INVERTER DRIVES<br />
This line legend must be<br />
highlighted<br />
Current reading<br />
h<br />
WARNING!! In the following steps all procedures must be followed exactly or grave bodily injury<br />
or equipment damage may occur. Make sure, “E-Stop” is pressed in, power off before proceeding.<br />
If the machine moves in the wrong direction, make corrections as in paragraph 2-3B above.<br />
NOTE: Prior to performing this test, if the inverter/s are run for the first time, Paragraph 2-8 through 2-11<br />
must be complied with or the respective inverter/s will not talk to the computer nor answer commands by<br />
the operator.<br />
WARNING! This test procedure allows the maintenance person direct control of the inverter drive circuits.<br />
There are ”NO SAFEGUARDS” available when these tests are performed. In other words if you<br />
accidentally activate pitch or roll while in the complete down position, you will drive the cockpit and/or<br />
platform into the ground or leveling stands. No one is allowed inside the rotation plane of the platform as<br />
long as this test window is active.<br />
To perform manual inverter drive tests in the following axis these steps must be followed exactly:<br />
1.) Ensure that the “E-Stop” is pressed in, power off to inverters.<br />
2.) Double click on “Mitsubishi Inverter Test” icon on the desktop or go to program icon. This<br />
opens the test window for all the axes.