29<br />

5.5.2 Notes on water installation<br />

Water supply<br />

The water supply is to be carried out according to the figure found in chapter 5.5.1 and the applicable<br />

local regulations for water installations. The indicated connection specifications must be observed.<br />

– The installation of the filter valve (accessory “Z261”, alternatively a shut-off valve and a 5 µm<br />

water filter can be used) should be made as close as possible to the steam generator.<br />

– Admissible mains pressure 1.0 to 10.0 bar (hammer-free system)<br />

For mains pressures >10 bar, the connection must be made via a pressure reducing valve (adjusted<br />

to 1.0 bar). For mains pressures