– StandbyDelay: Setting the period of time in standby operation after which an automatic<br />
cylinder draining takes place.<br />
Factory setting: 72 hours<br />
Setting range: 1...720 hours<br />
– Force Drain: Activating/Deactivating the forced draining which takes place after a certain<br />
time of operation. The forced draining takes place also during steam<br />
production.<br />
Factory setting: Off<br />
Options:<br />
On (Forced draining activated)<br />
Off (Forced draining deactivated)<br />
– Force Delay: Setting the time of operation after which a forced draining takes place.<br />
Factory setting: 72 hours<br />
Setting range: 1...720 hours<br />
6.6.4.10 Performing remote relay tests<br />
Settings<br />
GFCI-Mode :Aus<br />
Water Manag.:Set<br />
Remote Test :Set<br />
Bath Test :Set<br />
Contrast :15<br />
Esc<br />
Set<br />
Select “Remote Test” in the settings menu, then press the key.<br />
Remote Test<br />
Remote Steam:<br />
Off<br />
Esc<br />
Set<br />
Remote Service:<br />
Off 12.00.00<br />
Remote Error:<br />
Off<br />
Remote Unit On:<br />
On.11.2006 12.00.00<br />
The list with the remote relay tests appears, the first relay test is<br />
shown.<br />
Press the < > and < > keys in order to select the further relay tests<br />
available and press the key to activate/deactivate the corresponding<br />
relay for testing.