29.01.2015 Views

dectron_design - RJI-Sales.com

dectron_design - RJI-Sales.com

dectron_design - RJI-Sales.com

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Electrical Data<br />

Natatorium<br />

Example :<br />

DS-150, 460/3/60, with 13,500 CFM supply air at 2.0"<br />

ESP, 3000 CFM minimum outdoor air with Smart Saver<br />

Heat Recovery coils and Purge fan.<br />

Step #1 :<br />

Select supply motor horsepower from page 10 = 15 HP<br />

Model CFM Blower ESP HP<br />

1 10<br />

150/152 13500 22-22BI<br />

2 15<br />

Step #2 :<br />

Select exhaust fan #1 (EF#1) horsepower from<br />

page 10 = 3000 CFM OA + 10% = 3300 CFM EA = 3 HP<br />

EF#1 with Smart Saver Heat Recovery Coils<br />

INDOOR Unit<br />

OUTDOOR Unit<br />

Blower 1" ESP 0.5" ESP<br />

CFM HP CFM HP<br />

12-9 2900-3600 3 2900-3500 3<br />

Step #3: (only for Purge units)<br />

Select exhaust fan #2 (EF#2) horsepower from page<br />

10 = 13500 CFM – 3300 CFM = 10200 CFM + 10% =<br />

11220 CFM = 7.5 HP<br />

INDOOR Unit<br />

EF#1 and EF#2<br />

OUTDOOR Unit<br />

Blower 1" ESP 0.5" ESP<br />

CFM HP CFM HP<br />

20-20 10000-13000 7.5 9400-13000 7.5<br />

Step #4 :<br />

Look up the selected 15 HP + 3 HP <strong>com</strong>bination in the following<br />

electrical data section for unit MCA and MOP ratings<br />

Field<br />

Unit SA EF1 EF2 Unit Unit<br />

Volt-ph-Hz<br />

Size<br />

HP HP HP MCA MOP Wire<br />

Size*<br />

150 460-3-60 15 3 N/A 89 125 3<br />

Note: EF2 does not figure in the MCA and MOP<br />

calculations as it only runs when the<br />

<strong>com</strong>pressor is off.<br />

Step #5 :<br />

Look up the motor amperes on page 17<br />

Blower motor rating in amperes (FLA)<br />

HP<br />

Power Supply ( Volt-ph-Hz)<br />

208-1-60 230-1-60 208-3-60 230-3-60 460-3-60 575-3-60<br />

3 N/A 16.9 8.4 8.4 4.2 3.4<br />

7.5 N/A 36.0 20.7 19.6 9.8 7.8<br />

15 N/A N/A 40.5 37.6 18.8 15.0<br />

Step #6 :<br />

Look up the <strong>com</strong>pressor amperes on page 17<br />

Compressor rating 1<br />

Across Part Winding<br />

Unit<br />

Volt-ph-Hz Qty the line Start*<br />

Size<br />

RLA LRA RLA LRA<br />

150 460-3-60 1 52.5 283.0 - -<br />

Note: For electrical rating on units with integral boiler and/or integral condenser, please contact the factory.<br />

ENERGY RECYCLING DEHUMIDIFIERS & POOL WATER HEATERS FOR NATATORIUMS<br />

11