Electrical Data<br />
Natatorium<br />
Example :<br />
DS-150, 460/3/60, with 13,500 CFM supply air at 2.0"<br />
ESP, 3000 CFM minimum outdoor air with Smart Saver<br />
Heat Recovery coils and Purge fan.<br />
Step #1 :<br />
Select supply motor horsepower from page 10 = 15 HP<br />
Model CFM Blower ESP HP<br />
1 10<br />
150/152 13500 22-22BI<br />
2 15<br />
Step #2 :<br />
Select exhaust fan #1 (EF#1) horsepower from<br />
page 10 = 3000 CFM OA + 10% = 3300 CFM EA = 3 HP<br />
EF#1 with Smart Saver Heat Recovery Coils<br />
INDOOR Unit<br />
OUTDOOR Unit<br />
Blower 1" ESP 0.5" ESP<br />
CFM HP CFM HP<br />
12-9 2900-3600 3 2900-3500 3<br />
Step #3: (only for Purge units)<br />
Select exhaust fan #2 (EF#2) horsepower from page<br />
10 = 13500 CFM – 3300 CFM = 10200 CFM + 10% =<br />
11220 CFM = 7.5 HP<br />
INDOOR Unit<br />
EF#1 and EF#2<br />
OUTDOOR Unit<br />
Blower 1" ESP 0.5" ESP<br />
CFM HP CFM HP<br />
20-20 10000-13000 7.5 9400-13000 7.5<br />
Step #4 :<br />
Look up the selected 15 HP + 3 HP <strong>com</strong>bination in the following<br />
electrical data section for unit MCA and MOP ratings<br />
Field<br />
Unit SA EF1 EF2 Unit Unit<br />
Volt-ph-Hz<br />
Size<br />
HP HP HP MCA MOP Wire<br />
Size*<br />
150 460-3-60 15 3 N/A 89 125 3<br />
Note: EF2 does not figure in the MCA and MOP<br />
calculations as it only runs when the<br />
<strong>com</strong>pressor is off.<br />
Step #5 :<br />
Look up the motor amperes on page 17<br />
Blower motor rating in amperes (FLA)<br />
HP<br />
Power Supply ( Volt-ph-Hz)<br />
208-1-60 230-1-60 208-3-60 230-3-60 460-3-60 575-3-60<br />
3 N/A 16.9 8.4 8.4 4.2 3.4<br />
7.5 N/A 36.0 20.7 19.6 9.8 7.8<br />
15 N/A N/A 40.5 37.6 18.8 15.0<br />
Step #6 :<br />
Look up the <strong>com</strong>pressor amperes on page 17<br />
Compressor rating 1<br />
Across Part Winding<br />
Unit<br />
Volt-ph-Hz Qty the line Start*<br />
Size<br />
RLA LRA RLA LRA<br />
150 460-3-60 1 52.5 283.0 - -<br />
Note: For electrical rating on units with integral boiler and/or integral condenser, please contact the factory.<br />
ENERGY RECYCLING DEHUMIDIFIERS & POOL WATER HEATERS FOR NATATORIUMS<br />
11