Sequence of Operation<br />

Natatorium<br />

Sequence of Operation for DS/RS One Compressor Unit<br />

with Purge Mode Configuration<br />

Supply Air Blower<br />

Blower operation is continuous to prevent<br />

humidity stagnation. It can be<br />

remotely controlled by a Building<br />

Management System (BMS) signal.<br />

Blower stops and all (optional) motorized<br />

dampers close on:<br />

•power failure<br />

•firestat alarm<br />

•freezestat alarm<br />

•remote off control<br />

(manual or from BMS)<br />

Exhaust Air Blowers (EF1 & EF2)<br />

Blowers can be unit mounted or<br />

remote.<br />

EF1 blower operation is continuous or<br />

can be controlled by an occupied/unoccupied<br />

signal from the BMS, a<br />

seven-day time clock or through the<br />

microprocessor in the DRY-O-TRON®.<br />

EF1 exhausts 10% more air than is<br />

introduced through the outdoor air<br />

opening at minimum set point to<br />

maintain a negative space pressure.<br />

EF2 operates only on call for Purge<br />

mode or Economizer mode.<br />

Blowers stop and all (optional) motorized<br />

dampers close on:<br />

•power failure<br />

•firestat alarm<br />

•freezestat alarm<br />

•remote off control<br />

(manual or from BMS)<br />

Outdoor Air Damper<br />

Standard manual damper is normally<br />

closed (unoccupied mode).<br />

On an occupied signal from the sevenday<br />

time clock, the damper opens to<br />

the minimum set point. Outdoor air is<br />

introduced to meet local code requirements.<br />

On Purge mode signal, the damper<br />

opens fully to allow 100% outdoor air<br />

into the DRY-O-TRON®.<br />

All motorized dampers close on supply<br />

air blower stop.<br />

Dehumidification Mode<br />

Dehumidification mode occurs when<br />

the room relative humidity rises above<br />

set point (i.e. 50% RH).<br />

• The outdoor air sensors on DOTICS-<br />

9 controller only, (temperature and<br />

% RH) will verify if Economizer<br />

dehumidification is possible.<br />

• If outdoor air is not suitable for<br />

Economizer operation, the <strong>com</strong>pressor<br />

starts to operate in “dehumidification<br />

and hot gas reheat mode".<br />

The hot gas reheat coil is energized.<br />

Pool Water Heating Mode<br />

Pool water heating mode occurs when<br />

the pool water temperature drops<br />

below set point.<br />

• If the <strong>com</strong>pressor is already operating<br />

in dehumidification or cooling<br />

mode, the <strong>com</strong>pressor hot gas is<br />

used for water heating.<br />

• If all room conditions are satisfied,<br />

or if there is a call for second-stage<br />

pool water heating, the microprocessor<br />

will send a signal to the<br />

auxiliary pool water heater to maintain<br />

water temperature.<br />

• Dectron Inc.’s Water Smart Design<br />

will ensure <strong>com</strong>pressor operation in<br />

dehumidification mode. Cooling<br />

mode is never interrupted by a lack<br />

of water flow to the unit.<br />

• Should water flow be interrupted,<br />

the microprocessor will lock out<br />

water heating mode and display<br />

“low water flow" message on the<br />

operator panel. All other modes of<br />

operation will operate normally.<br />

Cooling Mode<br />

Cooling mode occurs when the space<br />

temperature is above set point.<br />

• The outdoor air sensor verifies if<br />

Economizer cooling is possible.<br />

• If outdoor air is not suitable for<br />

Economizer cooling, the <strong>com</strong>pressor<br />

starts to operate in “cooling mode".<br />

Both the outdoor air-cooled and<br />

water-cooled condensers reject the<br />

<strong>com</strong>pressors’ Total Heat of Rejection<br />

as required.<br />

Economizer Mode<br />

Economizer mode will operate whenever<br />

outdoor conditions permit and<br />

override <strong>com</strong>pressor operation.<br />

• If cooling is called for, the microprocessor<br />

will verify that the outdoor<br />

temperature is suitable. If yes,<br />

and the outdoor humidity level is<br />

neutral to the space, the unit will<br />

operate in Economizer cooling<br />

mode.<br />

• If dehumidification is called for, the<br />

microprocessor (DOTICS-9 only) will<br />

verify that the outdoor moisture<br />

level is suitable. If it is and the outdoor<br />

temperature is neutral to the<br />

space, the unit will operate in<br />

Economizer dehumidification.<br />

• During Economizer mode, the<br />

motorized O/A damper opens to<br />

100% and R/A dampers (evaporator<br />

face and bypass damper) fully close.<br />

Supply fan and exhaust fans (EF1<br />

and EF2) ventilate the space with<br />

100% outdoor air.<br />

Space Heating Mode<br />

Heating mode occurs when the space<br />

temperature drops below set point.<br />

• If the room temperature drops below<br />

set point, the DRY-O-TRON®’s<br />

microprocessor will send a signal to<br />

a space-heating coil (factory mounted<br />

or remote) to maintain space<br />

temperature.<br />

• Optional unit mounted heating coil<br />

freeze protection mode. If the heating<br />

coil’s average leaving air temperature<br />

falls below 45°F/7.2°C<br />

(adjustable), the blowers shut down,<br />

all dampers close and the control<br />

valves will fully open.<br />

Purge Mode<br />

Purge mode occurs on a call for Purge<br />

mode from DRY-O-TRON® operator<br />

panel or remote push button (by others)<br />

momentary signal. This timeroperated<br />

mode (2-20 minutes) is<br />

intended to ventilate the space with<br />

one <strong>com</strong>plete air change and then<br />

automatically resume normal operation.<br />

• DRY-O-TRON® <strong>com</strong>pressors are<br />

stopped.<br />

• Face and bypass dampers on evaporator<br />

coil close fully.<br />

• Outdoor air damper opens fully to<br />

allow 100% outdoor air into the<br />

DRY-O-TRON®.<br />

• EF1 and EF2 operate to evacuate<br />

maximum air flow from the space.<br />

• The space heating coil will temper<br />

the supply air as required.<br />

ENERGY RECYCLING DEHUMIDIFIERS & POOL WATER HEATERS FOR NATATORIUMS<br />