Sequence of Operation<br />
Natatorium<br />
Sequence of Operation for DS/RS One Compressor Unit<br />
with Purge Mode Configuration<br />
Supply Air Blower<br />
Blower operation is continuous to prevent<br />
humidity stagnation. It can be<br />
remotely controlled by a Building<br />
Management System (BMS) signal.<br />
Blower stops and all (optional) motorized<br />
dampers close on:<br />
•power failure<br />
•firestat alarm<br />
•freezestat alarm<br />
•remote off control<br />
(manual or from BMS)<br />
Exhaust Air Blowers (EF1 & EF2)<br />
Blowers can be unit mounted or<br />
remote.<br />
EF1 blower operation is continuous or<br />
can be controlled by an occupied/unoccupied<br />
signal from the BMS, a<br />
seven-day time clock or through the<br />
microprocessor in the DRY-O-TRON®.<br />
EF1 exhausts 10% more air than is<br />
introduced through the outdoor air<br />
opening at minimum set point to<br />
maintain a negative space pressure.<br />
EF2 operates only on call for Purge<br />
mode or Economizer mode.<br />
Blowers stop and all (optional) motorized<br />
dampers close on:<br />
•power failure<br />
•firestat alarm<br />
•freezestat alarm<br />
•remote off control<br />
(manual or from BMS)<br />
Outdoor Air Damper<br />
Standard manual damper is normally<br />
closed (unoccupied mode).<br />
On an occupied signal from the sevenday<br />
time clock, the damper opens to<br />
the minimum set point. Outdoor air is<br />
introduced to meet local code requirements.<br />
On Purge mode signal, the damper<br />
opens fully to allow 100% outdoor air<br />
into the DRY-O-TRON®.<br />
All motorized dampers close on supply<br />
air blower stop.<br />
Dehumidification Mode<br />
Dehumidification mode occurs when<br />
the room relative humidity rises above<br />
set point (i.e. 50% RH).<br />
• The outdoor air sensors on DOTICS-<br />
9 controller only, (temperature and<br />
% RH) will verify if Economizer<br />
dehumidification is possible.<br />
• If outdoor air is not suitable for<br />
Economizer operation, the <strong>com</strong>pressor<br />
starts to operate in “dehumidification<br />
and hot gas reheat mode".<br />
The hot gas reheat coil is energized.<br />
Pool Water Heating Mode<br />
Pool water heating mode occurs when<br />
the pool water temperature drops<br />
below set point.<br />
• If the <strong>com</strong>pressor is already operating<br />
in dehumidification or cooling<br />
mode, the <strong>com</strong>pressor hot gas is<br />
used for water heating.<br />
• If all room conditions are satisfied,<br />
or if there is a call for second-stage<br />
pool water heating, the microprocessor<br />
will send a signal to the<br />
auxiliary pool water heater to maintain<br />
water temperature.<br />
• Dectron Inc.’s Water Smart Design<br />
will ensure <strong>com</strong>pressor operation in<br />
dehumidification mode. Cooling<br />
mode is never interrupted by a lack<br />
of water flow to the unit.<br />
• Should water flow be interrupted,<br />
the microprocessor will lock out<br />
water heating mode and display<br />
“low water flow" message on the<br />
operator panel. All other modes of<br />
operation will operate normally.<br />
Cooling Mode<br />
Cooling mode occurs when the space<br />
temperature is above set point.<br />
• The outdoor air sensor verifies if<br />
Economizer cooling is possible.<br />
• If outdoor air is not suitable for<br />
Economizer cooling, the <strong>com</strong>pressor<br />
starts to operate in “cooling mode".<br />
Both the outdoor air-cooled and<br />
water-cooled condensers reject the<br />
<strong>com</strong>pressors’ Total Heat of Rejection<br />
as required.<br />
Economizer Mode<br />
Economizer mode will operate whenever<br />
outdoor conditions permit and<br />
override <strong>com</strong>pressor operation.<br />
• If cooling is called for, the microprocessor<br />
will verify that the outdoor<br />
temperature is suitable. If yes,<br />
and the outdoor humidity level is<br />
neutral to the space, the unit will<br />
operate in Economizer cooling<br />
mode.<br />
• If dehumidification is called for, the<br />
microprocessor (DOTICS-9 only) will<br />
verify that the outdoor moisture<br />
level is suitable. If it is and the outdoor<br />
temperature is neutral to the<br />
space, the unit will operate in<br />
Economizer dehumidification.<br />
• During Economizer mode, the<br />
motorized O/A damper opens to<br />
100% and R/A dampers (evaporator<br />
face and bypass damper) fully close.<br />
Supply fan and exhaust fans (EF1<br />
and EF2) ventilate the space with<br />
100% outdoor air.<br />
Space Heating Mode<br />
Heating mode occurs when the space<br />
temperature drops below set point.<br />
• If the room temperature drops below<br />
set point, the DRY-O-TRON®’s<br />
microprocessor will send a signal to<br />
a space-heating coil (factory mounted<br />
or remote) to maintain space<br />
temperature.<br />
• Optional unit mounted heating coil<br />
freeze protection mode. If the heating<br />
coil’s average leaving air temperature<br />
falls below 45°F/7.2°C<br />
(adjustable), the blowers shut down,<br />
all dampers close and the control<br />
valves will fully open.<br />
Purge Mode<br />
Purge mode occurs on a call for Purge<br />
mode from DRY-O-TRON® operator<br />
panel or remote push button (by others)<br />
momentary signal. This timeroperated<br />
mode (2-20 minutes) is<br />
intended to ventilate the space with<br />
one <strong>com</strong>plete air change and then<br />
automatically resume normal operation.<br />
• DRY-O-TRON® <strong>com</strong>pressors are<br />
stopped.<br />
• Face and bypass dampers on evaporator<br />
coil close fully.<br />
• Outdoor air damper opens fully to<br />
allow 100% outdoor air into the<br />
DRY-O-TRON®.<br />
• EF1 and EF2 operate to evacuate<br />
maximum air flow from the space.<br />
• The space heating coil will temper<br />
the supply air as required.<br />
ENERGY RECYCLING DEHUMIDIFIERS & POOL WATER HEATERS FOR NATATORIUMS<br />