Performance Data<br />

Natatorium<br />

Smart Saver Heat Recovery Coils<br />

Any DRY-O-TRON® that has an exhaust<br />

fan option can also have the<br />

Smart Saver heat recovery coils option.<br />

These coils extract the heat from the<br />

exhaust air stream and transfer it to<br />

the outdoor air stream using a passive<br />

refrigerant system loop. The heat<br />

recovery coils are charged with R-22.<br />

Due to the nature of the refrigerant<br />

with its high volumetric difference<br />

between liquid and gas (1:40), the<br />

recovery system does not require any<br />

mechanical moving parts.<br />

The coils are arranged so that the<br />

refrigerant in the condenser coil (outdoor<br />

air intake) drains into the evaporator<br />

coil (exhaust air).<br />

The heat recovered is determined by<br />

the temperature difference between<br />

indoor air and outdoor air. Here below<br />

is a quick and simple procedure to<br />

calculate the savings :<br />

DRY-O-TRON ® Smart Saver Heat Recovery Coils Payback Analysis<br />

POOL LOCATION : Chicago Bin Data (see table at right)<br />

(T1) O/A average temp : 51 °F (10.5°C)<br />

(T2) Winter <strong>design</strong> temp : -8 °F (-22°C)<br />

(T3) Indoor <strong>design</strong> temp : 82 °F (27.7°C)<br />

(V) O/A volume : 4500 CFM<br />

(N) Occupied hours : 12 hours<br />

Energy cost :<br />

0.55$/100,000 Btu<br />

(n) Energy efficiency : 80% (Efficiency of space heating system)<br />

(hre) Heat recovery efficiency : 50 %<br />

Annual heat recovered :<br />

Q = (T3-T1)*1.08*V*(8760*N/24)*hre<br />

= 329,945,400 Btu per year<br />

Annual savings :<br />

= (Q*$/100,000 Btu)/n = $2,268.37 per year<br />

Reduction in space heating : = (T3-T2)*1.08*V*hre = 218,700 Btu/h<br />

In most applications, the average payback is in the two-year range.<br />

Outdoor air represents a major wintertime heating load. The energy recovered<br />

by the DRY-O-TRON® Smart Saver heat recovery coils cuts that load in half. This<br />

can be a noteworthy initial cost saving in the space heating system as well.<br />

Contact Dectron Inc. for your copy of our quick calculation software.<br />

City<br />

Average Winter<br />

° F DB 1 ° F DB 2<br />

Albuquerque 57 12<br />

Amarillo 57 6<br />

Atlanta 61 17<br />

Birmingham 62 17<br />

Bismarck 42 -23<br />

Boise 51 3<br />

Boston 51 6<br />

Brownsville 73 36<br />

Buffalo 43 2<br />

Charleston 64 24<br />

Cheyenne 46 -9<br />

Chicago 51 -8<br />

Cleveland 50 1<br />

Dallas 65 18<br />

Dayton 52 -1<br />

Denver 50 -5<br />

Des Moines 50 -10<br />

Detroit 49 3<br />

Dodge City 54 0<br />

Edmonton 35 -29<br />

El Paso 64 20<br />

Great Falls 45 -21<br />

Indianapolis 52 -2<br />

Kansas City 56 2<br />

Lake Charles 68 9<br />

Las Vegas 66 25<br />

Los Angeles 61 41<br />

Medford 52 19<br />

Miami 75 7<br />

Minneapolis 45 -16<br />

Montreal 44 -16<br />

Nashville 60 9<br />

New York 54 11<br />

Oklahoma City 60 9<br />

Omaha 51 -8<br />

Phoenix 72 31<br />

Pittsburgh 50 3<br />

Portland, ME 46 -6<br />

Portland, OR 53 17<br />

Salt Lake City 52 3<br />

San Antonio 68 25<br />

Seattle 51 20<br />

St Louis 55 2<br />

Tampa 71 19<br />

Tallahassee 67 27<br />

Toronto 46 -5<br />

1<br />

Per ASHRAE bin data<br />

2<br />

99% <strong>design</strong><br />

ENERGY RECYCLING DEHUMIDIFIERS & POOL WATER HEATERS FOR NATATORIUMS<br />

25