Natatorium<br />
Performance Data<br />
Auxiliary Space and Pool Water Heat - Gas Boilers<br />
Dectron has chosen to <strong>design</strong> its auxiliary<br />
gas heat option in the form of<br />
an outdoor boiler supplying glycol to<br />
a unit mounted hot water coil. The<br />
primary reason is safety. If chloramine<br />
laden air were ever to be introduced<br />
to the <strong>com</strong>bustion air stream, the<br />
result would be the production of<br />
hydrochloric (HCL) acid. This will<br />
never occur with our outdoor boiler<br />
<strong>design</strong>, resulting in peace of mind and<br />
reduced liability for the system<br />
<strong>design</strong>er. With a 1:5 turndown, it also<br />
gives Dectron Inc. superior control of<br />
the supply air temperature.<br />
Another benefit of the boiler <strong>design</strong><br />
is that it can also be sized to provide<br />
auxiliary pool water heating in addition<br />
to the space heating. This means<br />
that the seasonal shutdown of existing<br />
boilers is possible in retrofit applications.<br />
Outdoor DRY-O-TRON®s can be packaged<br />
with an integral boiler which<br />
includes factory-mounted pump kit<br />
and expansion tank. They are factory<br />
charged with a mixture of 50% deionized<br />
water, 47.5% ethylene glycol and<br />
2.5% DowTherm® anti-corrosion<br />
package for -30° F (-34° C) and factory<br />
tested.<br />
Available Gas Boiler Capacities<br />
MBH Natural Gas<br />
Indoor DRY-O-TRON®s can be field<br />
piped with remote boilers that <strong>com</strong>e<br />
with factory supplied expansion tank<br />
kit and pump. External piping, valves<br />
and glycol are by others.<br />
Gas Glycol Pump Amps Add<br />
Input Output conn. conn. 208/ Boiler Weight<br />
(MBH) (MBH) inches NPT 230V 460V 575V Model (lb.)<br />
181 148 3<br />
/4 1 1 /2 2.4 1.2 1.0 H182 620<br />
264 216 3<br />
/4 1 1 /2 2.4 1.2 1.0 H260 680<br />
334 274 3<br />
/4 1 1 /2 3.2 1.6 1.2 H330 770<br />
399 327 3<br />
/4 1 1 /2 3.2 1.6 1.2 H400 870<br />
511 419 1 2 4.2 2.1 1.7 H514 990<br />
627 514 1 2 4.2 2.1 1.7 H624 1120<br />
726 595 1 2 4.2 2.1 1.7 H724 1260<br />
825 676 1 2 4.2 2.1 1.7 H824 1410<br />
926 759 1 2 1 /2 4.2 2.1 1.7 H926 1590<br />
1083 888 1 1 /4 2 1 /2 5.6 2.8 2.3 H1083 1810<br />
1178 968 1 1 /4 3 5.6 2.8 2.3 H1178 2230<br />
1287 1055 1 1 /4 3 5.6 2.8 2.3 H1287 2400<br />
1413 1158 1 1 /4 3 8.8 4.4 3.9 H1414 2610<br />
1570 1287 1 1 /4 3 8.8 4.4 3.9 H1571 2820<br />
1758 1441 1 1 /4 3 8.8 4.4 3.9 H1758 3000<br />
Ratings shown are for elevations up to 2000 feet (609.6 m). Elevations over 2000 feet<br />
(609.6 m) ratings should be reduced at the rate of 4% for each additional 1000 feet (305 m)<br />
above sea level. For propane gas, please contact factory.<br />
Glycol Flow Diagram for H.W. Coil<br />
and Aux. Pool Water Heater<br />
(0.5 PSIG 14” WC max gas pressure)<br />
(0.25 PSIG 7” WC min gas pressure)<br />
ENERGY RECYCLING DEHUMIDIFIERS & POOL WATER HEATERS FOR NATATORIUMS<br />