29.01.2015 Views

dectron_design - RJI-Sales.com

dectron_design - RJI-Sales.com

dectron_design - RJI-Sales.com

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Natatorium<br />

Performance Data<br />

Auxiliary Space and Pool Water Heat - Gas Boilers<br />

Dectron has chosen to <strong>design</strong> its auxiliary<br />

gas heat option in the form of<br />

an outdoor boiler supplying glycol to<br />

a unit mounted hot water coil. The<br />

primary reason is safety. If chloramine<br />

laden air were ever to be introduced<br />

to the <strong>com</strong>bustion air stream, the<br />

result would be the production of<br />

hydrochloric (HCL) acid. This will<br />

never occur with our outdoor boiler<br />

<strong>design</strong>, resulting in peace of mind and<br />

reduced liability for the system<br />

<strong>design</strong>er. With a 1:5 turndown, it also<br />

gives Dectron Inc. superior control of<br />

the supply air temperature.<br />

Another benefit of the boiler <strong>design</strong><br />

is that it can also be sized to provide<br />

auxiliary pool water heating in addition<br />

to the space heating. This means<br />

that the seasonal shutdown of existing<br />

boilers is possible in retrofit applications.<br />

Outdoor DRY-O-TRON®s can be packaged<br />

with an integral boiler which<br />

includes factory-mounted pump kit<br />

and expansion tank. They are factory<br />

charged with a mixture of 50% deionized<br />

water, 47.5% ethylene glycol and<br />

2.5% DowTherm® anti-corrosion<br />

package for -30° F (-34° C) and factory<br />

tested.<br />

Available Gas Boiler Capacities<br />

MBH Natural Gas<br />

Indoor DRY-O-TRON®s can be field<br />

piped with remote boilers that <strong>com</strong>e<br />

with factory supplied expansion tank<br />

kit and pump. External piping, valves<br />

and glycol are by others.<br />

Gas Glycol Pump Amps Add<br />

Input Output conn. conn. 208/ Boiler Weight<br />

(MBH) (MBH) inches NPT 230V 460V 575V Model (lb.)<br />

181 148 3<br />

/4 1 1 /2 2.4 1.2 1.0 H182 620<br />

264 216 3<br />

/4 1 1 /2 2.4 1.2 1.0 H260 680<br />

334 274 3<br />

/4 1 1 /2 3.2 1.6 1.2 H330 770<br />

399 327 3<br />

/4 1 1 /2 3.2 1.6 1.2 H400 870<br />

511 419 1 2 4.2 2.1 1.7 H514 990<br />

627 514 1 2 4.2 2.1 1.7 H624 1120<br />

726 595 1 2 4.2 2.1 1.7 H724 1260<br />

825 676 1 2 4.2 2.1 1.7 H824 1410<br />

926 759 1 2 1 /2 4.2 2.1 1.7 H926 1590<br />

1083 888 1 1 /4 2 1 /2 5.6 2.8 2.3 H1083 1810<br />

1178 968 1 1 /4 3 5.6 2.8 2.3 H1178 2230<br />

1287 1055 1 1 /4 3 5.6 2.8 2.3 H1287 2400<br />

1413 1158 1 1 /4 3 8.8 4.4 3.9 H1414 2610<br />

1570 1287 1 1 /4 3 8.8 4.4 3.9 H1571 2820<br />

1758 1441 1 1 /4 3 8.8 4.4 3.9 H1758 3000<br />

Ratings shown are for elevations up to 2000 feet (609.6 m). Elevations over 2000 feet<br />

(609.6 m) ratings should be reduced at the rate of 4% for each additional 1000 feet (305 m)<br />

above sea level. For propane gas, please contact factory.<br />

Glycol Flow Diagram for H.W. Coil<br />

and Aux. Pool Water Heater<br />

(0.5 PSIG 14” WC max gas pressure)<br />

(0.25 PSIG 7” WC min gas pressure)<br />

ENERGY RECYCLING DEHUMIDIFIERS & POOL WATER HEATERS FOR NATATORIUMS<br />

31