Performance Data<br />

Natatorium<br />

Moisture Removal and Sensible Cooling Tables<br />

Model 182 - Moisture Removal Capacity in lb./h<br />

Return Air<br />

Relative Humidity<br />

Temperature 70% 60% 50% 40%<br />

74 °F 240.5 201.5 162.5 91.0<br />

75 °F 243.8 204.8 165.8 100.8<br />

76 °F 247.0 208.0 169.0 110.5<br />

77 °F 250.3 211.3 172.3 117.0<br />

78 °F 253.5 214.5 175.5 123.5<br />

79 °F 256.8 217.8 178.8 126.8<br />

80 °F 260.0 221.0 182.0 130.0<br />

81 °F 263.3 224.3 185.3 133.3<br />

82 °F 266.5 227.5 188.5 136.5<br />

83 °F 269.8 230.8 191.8 139.8<br />

84 °F 273.0 234.0 195.0 143.0<br />

85 °F 276.3 237.3 198.3 146.3<br />

86 °F 279.5 240.5 201.5 149.5<br />

Model 202 - Moisture Removal Capacity in lb./h<br />

Return Air<br />

Relative Humidity<br />

Temperature 70% 60% 50% 40%<br />

74 °F 268.3 224.8 181.3 101.5<br />

75 °F 271.9 228.4 184.9 112.4<br />

76 °F 275.5 232.0 188.5 123.3<br />

77 °F 279.1 235.6 192.1 130.5<br />

78 °F 282.8 239.3 195.8 137.8<br />

79 °F 286.4 242.9 199.4 141.4<br />

80 °F 290.0 246.5 203.0 145.0<br />

81 °F 293.6 250.1 206.6 148.6<br />

82 °F 297.3 253.8 210.3 152.3<br />

83 °F 300.9 257.4 213.9 155.9<br />

84 °F 304.5 261.0 217.5 159.5<br />

85 °F 308.1 264.6 221.1 163.1<br />

86 °F 311.8 268.3 224.8 166.8<br />

Model 242 - Moisture Removal Capacity in lb./h<br />

Return Air<br />

Relative Humidity<br />

Temperature 70% 60% 50% 40%<br />

74 °F 296.0 248.0 200.0 112.0<br />

75 °F 300.0 252.0 204.0 124.0<br />

76 °F 304.0 256.0 208.0 136.0<br />

77 °F 308.0 260.0 212.0 144.0<br />

78 °F 312.0 264.0 216.0 152.0<br />

79 °F 316.0 268.0 220.0 156.0<br />

80 °F 320.0 272.0 224.0 160.0<br />

81 °F 324.0 276.0 228.0 164.0<br />

82 °F 328.0 280.0 232.0 168.0<br />

83 °F 332.0 284.0 236.0 172.0<br />

84 °F 336.0 288.0 240.0 176.0<br />

85 °F 340.0 292.0 244.0 180.0<br />

86 °F 344.0 296.0 248.0 184.0<br />

Model 282 - Moisture Removal Capacity in lb./h<br />

Return Air<br />

Relative Humidity<br />

Temperature 70% 60% 50% 40%<br />

74 °F 360.8 302.3 243.8 136.5<br />

75 °F 365.6 307.1 248.6 151.1<br />

76 °F 370.5 312.0 253.5 165.8<br />

77 °F 375.4 316.9 258.4 175.5<br />

78 °F 380.3 321.8 263.3 185.3<br />

79 °F 385.1 326.6 268.1 190.1<br />

80 °F 390.0 331.5 273.0 195.0<br />

81 °F 394.9 336.4 277.9 199.9<br />

82 °F 399.8 341.3 282.8 204.8<br />

83 °F 404.6 346.1 287.6 209.6<br />

84 °F 409.5 351.0 292.5 214.5<br />

85 °F 414.4 355.9 297.4 219.4<br />

86 °F 419.3 360.8 302.3 224.3<br />

Model 182 - DX Coil Sensible Cooling in Btu/h<br />

Return Air<br />

Relative Humidity<br />

Temperature 70% 60% 50% 40%<br />

74 °F 281,460 309,600 334,150 343,980<br />

75 °F 277,970 307,390 339,070 351,840<br />

76 °F 274,470 305,190 341,720 358,720<br />

77 °F 270,970 302,970 340,810 363,640<br />

78 °F 267,480 300,740 339,910 373,450<br />

79 °F 263,940 298,530 339,010 373,230<br />

80 °F 260,400 296,310 338,120 373,010<br />

81 °F 257,450 294,100 337,190 372,830<br />

82 °F 254,510 291,890 336,260 372,650<br />

83 °F 251,560 289,670 335,360 372,440<br />

84 °F 248,610 287,440 334,460 372,240<br />

85 °F 245,660 285,010 333,540 372,030<br />

86 °F 242,710 283,050 332,620 371,810<br />

Model 202 - DX Coil Sensible Cooling in Btu/h<br />

Return Air<br />

Relative Humidity<br />

Temperature 70% 60% 50% 40%<br />

74 °F 313,940 345,320 372,710 383,670<br />

75 °F 310,040 342,860 378,190 392,440<br />

76 °F 306,140 340,400 381,150 400,110<br />

77 °F 302,240 337,920 380,140 405,590<br />

78 °F 298,340 335,440 379,130 416,540<br />

79 °F 294,390 332,970 378,130 416,300<br />

80 °F 290,450 330,500 377,130 416,050<br />

81 °F 287,160 328,030 376,090 415,850<br />

82 °F 283,870 325,570 375,060 415,640<br />

83 °F 280,580 323,090 374,060 415,420<br />

84 °F 277,300 320,610 373,060 415,190<br />

85 °F 274,010 317,900 372,030 414,950<br />

86 °F 270,720 315,710 371,000 414,710<br />

Model 242 - DX Coil Sensible Cooling in Btu/h<br />

Return Air<br />

Relative Humidity<br />

Temperature 70% 60% 50% 40%<br />

74 °F 346,420 381,040 411,260 423,360<br />

75 °F 342,110 378,330 417,310 433,040<br />

76 °F 337,810 375,620 420,580 441,500<br />

77 °F 333,500 372,880 419,460 447,550<br />

78 °F 329,200 370,140 418,350 459,630<br />

79 °F 324,850 367,420 417,250 459,360<br />

80 °F 320,500 364,690 416,140 459,090<br />

81 °F 316,870 361,970 415,000 458,860<br />

82 °F 313,240 359,250 413,860 458,640<br />

83 °F 309,610 356,510 412,750 458,390<br />

84 °F 305,980 353,780 411,650 458,140<br />

85 °F 302,350 350,780 410,510 457,880<br />

86 °F 298,720 348,360 409,380 457,620<br />

Model 282 - DX Coil Sensible Cooling in Btu/h<br />

Return Air<br />

Relative Humidity<br />

Temperature 70% 60% 50% 40%<br />

74 °F 422,190 464,390 501,230 515,970<br />

75 °F 416,950 461,090 508,600 527,760<br />

76 °F 411,700 457,780 512,580 538,080<br />

77 °F 406,460 454,450 511,220 545,450<br />

78 °F 401,210 451,110 509,870 560,180<br />

79 °F 395,910 447,790 508,520 559,850<br />

80 °F 390,600 444,460 507,180 559,510<br />

81 °F 386,180 441,150 505,780 559,240<br />

82 °F 381,760 437,830 504,390 558,970<br />

83 °F 377,340 434,500 503,040 558,670<br />

84 °F 372,910 431,160 501,700 558,360<br />

85 °F 368,490 427,520 500,310 558,040<br />

86 °F 364,070 424,570 498,930 557,720<br />

For NET sensible cooling values, please contact factory.<br />

ENERGY RECYCLING DEHUMIDIFIERS & POOL WATER HEATERS FOR NATATORIUMS<br />