Natatorium<br />

Heat Rejection Data<br />

Domestic Water Heater<br />

This heat rejection option does not provide air conditioning. It is a value-added option to take advantage of those hours<br />

when the DRY-O-TRON® is operating in dehumidification mode or minimum pool water-heating mode and/or air conditioning<br />

mode. The same vented, double wall, coaxial, water-cooled condensers are used for the pool water heaters<br />

since they are suitable for potable water applications.<br />

How Much Heat Can Be Obtained <br />

DRY-O-TRON®<br />

Domestic Water Heater<br />

Model GPM Conn.(MPT) Pool Heating Mode (Btu/h) Dehumidification Mode (Btu/h)<br />

080/100/102 20.0 1 1/4 56,000 96,000<br />

120/150 20.0 1 1/4 70,000 120,000<br />

122/152 30.0 1 1/2 84,000 144,000<br />

162/182 40.0 1 1/2 112,000 192,000<br />

202/242/282/362/482/562 40.0 1 1/2 140,000 240,000<br />

Domestic water heater capacities are stated at 100°F (37.7°C) leaving water temperature.<br />

Pressure drop = 6.0 psi for all models.<br />