Natatorium<br />
Heat Rejection Data<br />
Domestic Water Heater<br />
This heat rejection option does not provide air conditioning. It is a value-added option to take advantage of those hours<br />
when the DRY-O-TRON® is operating in dehumidification mode or minimum pool water-heating mode and/or air conditioning<br />
mode. The same vented, double wall, coaxial, water-cooled condensers are used for the pool water heaters<br />
since they are suitable for potable water applications.<br />
How Much Heat Can Be Obtained <br />
DRY-O-TRON®<br />
Domestic Water Heater<br />
Model GPM Conn.(MPT) Pool Heating Mode (Btu/h) Dehumidification Mode (Btu/h)<br />
080/100/102 20.0 1 1/4 56,000 96,000<br />
120/150 20.0 1 1/4 70,000 120,000<br />
122/152 30.0 1 1/2 84,000 144,000<br />
162/182 40.0 1 1/2 112,000 192,000<br />
202/242/282/362/482/562 40.0 1 1/2 140,000 240,000<br />
Domestic water heater capacities are stated at 100°F (37.7°C) leaving water temperature.<br />
Pressure drop = 6.0 psi for all models.<br />
Suggested Field Piping<br />
66 ENERGY RECYCLING DEHUMIDIFIERS & POOL WATER HEATERS FOR NATATORIUMS