5.3 Comparison of the shaking table test <strong>and</strong> the simulation<br />

5.3.1 Vibration properties<br />

The natural frequencies are in both cases very similar. The amplitude of the simulation is a little<br />

smaller than that of the shaking table test.<br />

5.3.2 Seismic excitation<br />

The Y direction response time history for the three dimensional Taft wave excitation is shown in<br />

Fig. 17. The amplitudes of the simulation are smaller than those of the table test. But acceleration<br />

<strong>and</strong> displacement are very similar. The similarity confirms the accuracy of the model.<br />

The maximum response acceleration ratio of the model at the maximum acceleration of the<br />

shaking table is shown in Table 4. In the cases of El Centro wave <strong>and</strong> Hachinohe wave the results<br />

are for one dimensional excitation. In the case of Taft wave those are for one, two <strong>and</strong> three<br />

dimensional excitation.<br />

The response acceleration ratio increased only a little bit horizontally, but vertically more for the<br />

three dimensional excitation than for the two dimensional one.<br />

Fig. 17 Y-direction time history response (for TAFT 3-D) Table 4 Maximum acceleration response amplitude<br />

6. CONCLUSION<br />

A four story building was designed <strong>and</strong> certified for the maximum response. From our<br />

investigations the following can be concluded.<br />

1) In the <strong>vibration</strong> isolated building supported by <strong>spring</strong>s <strong>and</strong> <strong>visco</strong>-elastic dampers <strong>vibration</strong> <strong>and</strong><br />

structure borne noise levels caused by traffic will be effectively reduced.<br />

2) The characteristics of the dampers can be modelled properly by a 4 parameter model<br />

respectively those of the <strong>spring</strong>s by a multi-direction shear <strong>spring</strong>.<br />

3) The 3 dimensional analysis of the models shows a good coincidence with the shaking table test,<br />

so that it can be used for analyzing a real building with a <strong>vibration</strong> <strong>isolation</strong> <strong>system</strong>.