Portection from overheating of power module<br />

• If the temperature of the heat sink TH. reaches over Toff, the Compressor stop instantly.<br />

• It will be limited the compressor operating frequency according to the heat sink TH.(refer to below FIG.)<br />

• It will be blink 4 times, when the thermistor is open or short, also the temperature is over Toff.<br />

T off °C<br />

T2 °C<br />

T1 °C<br />

T on °C<br />

COMP<br />

Freq.<br />

∆T = (T off - T on)<br />

T1 = T on + ∆T<br />

T2 = T on + 2 * ∆T<br />

Heat Sink Temp.<br />

Free Fc-1 Fc-2 Fc-1 Fc-2 OFF Free<br />

Portection from overheating of compressor<br />

Operation<br />

• If the temperature of the discharge pipe of compressor reaches over 130°C or below -30°C the compressor<br />

stop instantly.<br />

• It will be limited the compressor operating frequency according to the compressor dome TH.(Refer to below<br />

Fig.)<br />

• Temperature range by COMP SPEC varies by 10°C.<br />

D-Pipe Temp.<br />

∆T = (T off - T2)/2<br />

T1 = T2 + 2 * ∆T<br />

T3 = T2 + ∆T<br />

COMP Freq. Fh min Free Fc-1 Fc-2 OFF Fc-2 Fc-1 Free<br />

No. MODEL T on T off<br />

1 AS-W1863_ Series 85 95<br />

2 AS-W2463_ Series 85 95<br />

No. MODEL T on T off<br />

1 AS-W1863_ Series 98 108<br />

2 AS-W2463_ Series 98 108<br />

Service Manual 43