Troubleshooting Guide<br />

Trouble 6<br />

72 <strong>Room</strong> <strong>Air</strong> <strong>Conditioner</strong><br />

The heater does not operate at all.<br />

Turn off main power<br />

Check the wire connection of PTC Heater (Refer to Wiring Diagram)<br />

• Check the connecting condition of CN-PTC connector on the indor DC P.C.B Ass'y.<br />

• Check the soldering condition of CN-PTC connector on the indoor DC P.C.B Ass'y.<br />

Check the Heater driving Circuit.<br />

• Check the pattern between MICOM Pin No. 48 → IC02M Pin No. 7 → IC02M Pin No. 10 → CN-PTC<br />

If there is no problem result of all above check.<br />

• Inner side disconnection of PTC Heater unit or restriced operating condition of PTC Heater<br />

(pipe temp. is over 45°C, defrosting operation, compressor off, indoor fan off).