06.06.2015 Views

Manual Técnico - Chiller YORK® Absorção YPC ... - Johnson Controls

Manual Técnico - Chiller YORK® Absorção YPC ... - Johnson Controls

Manual Técnico - Chiller YORK® Absorção YPC ... - Johnson Controls

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

FORM 155.17-EG4<br />

Available Draft (Da) – The Available Draft is the draft<br />

required at the outlet exhaust flange of the YORK High<br />

Temperature Generator.<br />

Pressure Drop (dP) – Frictional losses in the chimney<br />

system which act against theoretical draft. The chimney<br />

draft needed to overcome chimney frictional losses<br />

is described as follows:<br />

Dt = dP + Da<br />

Proper chimney design balances the theoretical draft<br />

(Dt) against the pressure drop (dP) of the chimney system<br />

in order to provide the required available<br />

pressure(Da) at the outlet of the chiller-heater.<br />

Proper chimney design must provide the required (Da)<br />

under all operating conditions. Because the difference<br />

between summer and winter ambient conditions can result<br />

in Dt variations of 50% and greater, some method of<br />

draft control is usually required in order to maintain Da.<br />

Chimney Application – The YORK direct-fired chillerheater<br />

is equipped with a forced draft burner capable of<br />

firing on a variety of fuels, including natural gas and/or<br />

No. 2 oil and/or propane. As such, the unit will require a<br />

properly designed chimney system to control draft and<br />

discharge flue gases from the unit to the atmosphere.<br />

The combustion chamber of the chiller-heater is engineered<br />

to product a positive gauge pressure of 0.05 to<br />

0.15 in. of water (1.27 - 3.81 kg/m 2 ) at the outlet of the<br />

first stage generator with an exhaust temperature of<br />

400°F+/-50°F (204°C +/- 28°C). As such the chimney<br />

design must provide a method for maintaining the pressure<br />

at all ambient conditions. Because YORK<br />

chiller-heaters operate at “high fire” throughout the summer<br />

months, it is important to design the chimney system<br />

for summer ambient design conditions to avoid<br />

undersizing. It is recommended that the chimney itself<br />

should be designed for a Da of 0 (zero) in. (0 mm) of<br />

water column. This will prevent the chimney from becoming<br />

pressurized at any point along the flue gas path.<br />

Caution – If the stack/chimney pressure is ever<br />

above 0 (zero) in. of water column there<br />

is a chance of flue gas being leaked<br />

into the equipment room.<br />

There are two commonly used ways to maintain the<br />

pressure at the outlet of the chiller-heater. Either manual<br />

or automatic/motorized draft control can be used. All<br />

YORK direct-fired chiller-heaters will come standard with<br />

a manual draft control damper. This damper can be modified<br />

for motorized operation either in the factory (if ordered)<br />

or in the field if site conditions require.<br />

<strong>Manual</strong> Draft Control – <strong>Manual</strong> draft control is suitable<br />

for applications where each gas fired appliance will have<br />

its own dedicated chimney and draft control system. Fig.<br />

7 depicts a simple yet effective means of controlling draft.<br />

YORK INTERNATIONAL<br />

With this system, a (field supplied) barometric draft regulator<br />

is used in series with the factory supplied manual<br />

backdraft damper. With maximum economy employed<br />

in the chimney design, Dt would exactly equal dP + Da<br />

during the summer design ambient conditions with the<br />

barometric regulator closed. In reality, some degree of<br />

conservatism should exist in the design, causing the<br />

barometric regulator to be open slightly even during<br />

summer design conditions. As ambient temperatures<br />

drop, Dt would increase, if not for the barometric draft<br />

regulator. With the regulator in place, mechanical room<br />

air is introduced into the chimney system in response<br />

to the impressed draft, thus stabilizing the gauge pressure<br />

just upstream of the barometric regulator. Most<br />

barometric regulators can maintain -0.06 in. water column<br />

gauge pressure when properly sized for a particular<br />

application.<br />

With the gauge pressure stabilized upstream of the barometric<br />

regulator, the factory supplied manual backdraft<br />

damper can be adjusted to a fixed position which will<br />

provide the pressure drop to yield the required positive<br />

pressure at the exhaust flange of the chiller-heater.<br />

Motorized Draft Control – Motorized draft control is suitable<br />

for applications where multiple gas fired appliances<br />

will be ducted into one common chimney system. In this<br />

case each unit will require its own draft control system.<br />

(Motorized draft control may be used for one chiller-heater/one<br />

chimney applications as well if it is desired<br />

over manual control.) Fig. 8 depicts a sequential<br />

draft control system which incorporates a motorized<br />

damper whose position is automatically adjusted as a<br />

function of available draft at the outlet of the chiller. The<br />

YORK supplied backdraft damper at the outlet of the<br />

chiller can be modified (in the factory if ordered, or in<br />

the field) to mount the motor driver. The motor is controlled<br />

from a draft control panel which senses the pressure<br />

at the outlet of the chiller-heater. The draft control<br />

panel is available from YORK to ship with the chiller.<br />

The panel is wired to the burner panel and damper motor<br />

in the field, and the pressure is sensed through a small<br />

line field connected to the outlet of the chiller-heater.<br />

Special Problems and Maintenance – Factors causing<br />

draft variations during normal operation include: wind<br />

and weather factors, inadequate chimney construction<br />

or system installation, location of installation, or inadequate<br />

system maintenance.<br />

Wind and weather – Windy conditions will tend to increase<br />

the draft in the chimney as the wind helps to<br />

remove the combustion products leaving the chimney<br />

at a much faster rate. Down draft may occur causing a<br />

temporary positive pressure in the chimney system. The<br />

stack should be designed to prevent not only wind, but<br />

21

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!