LD01617<br />
FIG. 7 – BAROMETRIC CONTROL<br />
Gauge Pressure Profile – Chimney System with Barometric Control<br />
NOTES:<br />
1. dP between A and B due to transition<br />
piece and properly positioned<br />
backdraft damper. Damper adjusted<br />
to maintain +0.05 to +0.15 in. (+1.27<br />
to +3.81 kg/m 2 ) water at A.<br />
2. Maximum draft (minimum gauge<br />
pressure) occurs at base of vertical<br />
section of chimney (B). Barometric<br />
regulator will maintain steady gauge<br />
pressure at C. Maximum gauge<br />
pressure attainable with a barometric<br />
draft regulator is typically -0.06<br />
in. water (-1.52 kg/m 2 ).<br />
LD01618<br />