Ratings<br />

FORM 155.17-EG4<br />

COMPUTERIZED PERFORMANCE RATINGS<br />

Each chiller selection is custom-matched to meet the<br />

individual application requirements. It is not practical to<br />

provide tabulated information for all possible combinations.<br />

Computerized performance ratings are available<br />

through each YORK Sales Office.<br />

Fig. 1 details the high efficiency part load performance<br />

of the <strong>YPC</strong> Absorption <strong>Chiller</strong>. At both constant tower<br />

water temperatures and ARI adjusted entering tower<br />

temperatures, the unique Millennium design delivers superior<br />

economy at low loads.<br />

FIG. 1 – ENERGY INPUT VS. OUTPUT*<br />

LD01612<br />

* Shows the part load performance of the YORK <strong>YPC</strong> chiller-heater. The highest efficiency is achieved between 50 and 100 percent chilling<br />

capacity. Valid for leaving chilled water temperature 42°- 52°F (6.6°C - 12.2°C).<br />

FIG. 2 – IPLV ANALYSIS**<br />

WEIGHTING<br />

ENTERING COND.<br />

FACTOR WEIGHTED<br />

LOAD (%) WATER TEMP. COP<br />

(FROM ARI AVERAGE COP<br />

°F °C 560-92)<br />

100 85.00 29.44 1.0 0.17 0.170<br />

75 78.75 25.97 1.097 0.39 0.428<br />

50 72.50 22.64 1.167 0.33 0.385<br />

25 68.00 20.00 1.089 0.11 0.120<br />

** IPLV (expressed as a COP) = 1.10<br />

YORK INTERNATIONAL<br />

9