Ratings<br />
FORM 155.17-EG4<br />
COMPUTERIZED PERFORMANCE RATINGS<br />
Each chiller selection is custom-matched to meet the<br />
individual application requirements. It is not practical to<br />
provide tabulated information for all possible combinations.<br />
Computerized performance ratings are available<br />
through each YORK Sales Office.<br />
Fig. 1 details the high efficiency part load performance<br />
of the <strong>YPC</strong> Absorption <strong>Chiller</strong>. At both constant tower<br />
water temperatures and ARI adjusted entering tower<br />
temperatures, the unique Millennium design delivers superior<br />
economy at low loads.<br />
FIG. 1 – ENERGY INPUT VS. OUTPUT*<br />
LD01612<br />
* Shows the part load performance of the YORK <strong>YPC</strong> chiller-heater. The highest efficiency is achieved between 50 and 100 percent chilling<br />
capacity. Valid for leaving chilled water temperature 42°- 52°F (6.6°C - 12.2°C).<br />
FIG. 2 – IPLV ANALYSIS**<br />
WEIGHTING<br />
ENTERING COND.<br />
FACTOR WEIGHTED<br />
LOAD (%) WATER TEMP. COP<br />
(FROM ARI AVERAGE COP<br />
°F °C 560-92)<br />
100 85.00 29.44 1.0 0.17 0.170<br />
75 78.75 25.97 1.097 0.39 0.428<br />
50 72.50 22.64 1.167 0.33 0.385<br />
25 68.00 20.00 1.089 0.11 0.120<br />
** IPLV (expressed as a COP) = 1.10<br />
YORK INTERNATIONAL<br />
9