Nozzle Arrangements: 15SL and Larger<br />

FORM 155.17-EG4<br />

LD01623<br />

EVAPORATOR NOZZLE ARRANGEMENTS<br />

HEATER NOZZLE ARRANGEMENTS<br />

NO. OF<br />

PASSES<br />

3<br />

2, 4<br />

NOZZLE<br />

ARRANGEMENT<br />

IN<br />

OUT<br />

E1 A D<br />

E4 C B<br />

E5 A B<br />

E7 C D<br />

NO. OF<br />

NOZZLE<br />

PASSES ARRANGEMENT<br />

IN OUT<br />

1 HW1 R S<br />

2 HW2 P N<br />

3 HW3 Q N<br />

4 HW4 P N<br />

TOWER WATER NOZZLE ARRANGEMENTS<br />

NO. OF NOZZLE ABSORBER CONDENSER<br />

PASSES ARRANGEMENT IN OUT IN OUT<br />

1<br />

2<br />

3<br />

C1 F H M L<br />

C2 H F L M<br />

C3 E F L M<br />

C4 G H M L<br />

C1 E H M L<br />

C2 G F L M<br />

NOZZLE SIZES<br />

Same Notes as other Nozzle<br />

Arrangements apply. See pg. 26.<br />

EVAPORATOR ABS./COND. HIGH TEMP. HOT WATER HEATER<br />

<strong>YPC</strong>-DF<br />

NUMBER OF PASSES<br />

2 3 4 1* 2* 3* 1 2 3 4<br />

15SL/16S 8" 6" 6" N/A 10" 8" — 6" 6" 4"<br />

16SL/17S 8" 6" 6" N/A 10" 8" 8" 6" 6" —<br />

18S 8" 6" 6" N/A 10" 8" 8" 6" 6" —<br />

19S 8" 6" 6" 12" 10" 8" 8" 6" 6" —<br />

* Number of passes refers to the number of absorber passes only. The condenser is always one-pass with nozzle sizes that match the<br />