FORM 155.17-EG4<br />
Safety Shutdown systems. Also included shall be an<br />
operator interface concentration calculator. An operator<br />
shall be able to use the concentration calculator to<br />
determine concentration by inputting set of conditions.<br />
When an operator inputs any two of three parameters<br />
(bromide solution temperature, saturation temperature,<br />
and pressure) and the micropanel shall display the concentration.<br />
The display shall also indicate if the input<br />
conditions are in the crystallization zone.<br />
Data Logging – The ISN Millennium Control Center<br />
Panel shall contain an RS-232 port to enable the transmission<br />
of all operating, setpoint, and shutdown information<br />
to a remote printer (by others). This transmission<br />
can occur as needed or automatically on predetermined<br />
intervals.<br />
In the case of a safety or cycling shutdown, the RS-232<br />
port shall transmit all operating data detected prior to<br />
the shutdown as well as the time and cause of the shutdown.<br />
In addition, a history of the last four safety or<br />
cycling shutdowns, with the exception of power failures,<br />
shall be retained in memory and can be printed as well.<br />
Energy Management Interface – When connected to<br />
an Integrated Systems Network provided by the<br />
chiller-heater manufacturer, the ISN Millennium Control<br />
Center Panel shall be able to communicate all data<br />
accessible from the keypad to a remote integrated DDC<br />
processor through a single shielded cable. This information<br />
will include all unit temperatures, pressures,<br />
safety alarms, and status readouts for complete integrated<br />
plant control, data logging, and local/remote display<br />
of operator information. The single shielded cable<br />
shall also allow the remote integrated DDC processor<br />
to issue operating commands to the ISN Millennium<br />
Control Center including but not limited to the following:<br />
• Remote unit start/stop<br />
• Remote chilled-water temperature reset<br />
• Remote hot-water temperature reset<br />
The ISN Millennium Control Center Panel shall also be<br />
capable of providing a limited interface to other building<br />
automation systems in order to permit the following operations:<br />
• Remote unit start/stop<br />
• Remote chilled-water temperature reset<br />
• Remote hot-water temperature reset<br />
• Remote readout of status including<br />
• Unit ready to start<br />
• Unit operating<br />
• Unit safety shutdown<br />
• Unit cycling shutdown<br />