FORM 155.17-EG4<br />

Safety Shutdown systems. Also included shall be an<br />

operator interface concentration calculator. An operator<br />

shall be able to use the concentration calculator to<br />

determine concentration by inputting set of conditions.<br />

When an operator inputs any two of three parameters<br />

(bromide solution temperature, saturation temperature,<br />

and pressure) and the micropanel shall display the concentration.<br />

The display shall also indicate if the input<br />

conditions are in the crystallization zone.<br />

Data Logging – The ISN Millennium Control Center<br />

Panel shall contain an RS-232 port to enable the transmission<br />

of all operating, setpoint, and shutdown information<br />

to a remote printer (by others). This transmission<br />

can occur as needed or automatically on predetermined<br />

intervals.<br />

In the case of a safety or cycling shutdown, the RS-232<br />

port shall transmit all operating data detected prior to<br />

the shutdown as well as the time and cause of the shutdown.<br />

In addition, a history of the last four safety or<br />

cycling shutdowns, with the exception of power failures,<br />

shall be retained in memory and can be printed as well.<br />

Energy Management Interface – When connected to<br />

an Integrated Systems Network provided by the<br />

chiller-heater manufacturer, the ISN Millennium Control<br />

Center Panel shall be able to communicate all data<br />

accessible from the keypad to a remote integrated DDC<br />

processor through a single shielded cable. This information<br />

will include all unit temperatures, pressures,<br />

safety alarms, and status readouts for complete integrated<br />

plant control, data logging, and local/remote display<br />

of operator information. The single shielded cable<br />

shall also allow the remote integrated DDC processor<br />

to issue operating commands to the ISN Millennium<br />

Control Center including but not limited to the following:<br />

• Remote unit start/stop<br />

• Remote chilled-water temperature reset<br />

• Remote hot-water temperature reset<br />

The ISN Millennium Control Center Panel shall also be<br />

capable of providing a limited interface to other building<br />

automation systems in order to permit the following operations:<br />

• Remote unit start/stop<br />

• Remote chilled-water temperature reset<br />

• Remote hot-water temperature reset<br />

• Remote readout of status including<br />

• Unit ready to start<br />

• Unit operating<br />

• Unit safety shutdown<br />

• Unit cycling shutdown<br />