FORM 155.17-EG4<br />
ply; non-fused disconnect switch; motor starters, complete<br />
with current and thermal overload protection, for<br />
solution pump, refrigerant pump, and purge pump (current<br />
overloads only); and a 115VAC 50/60 Hz Control<br />
Power Transformer.<br />
Burner Control Panel – The Burner Control Panel enclosure<br />
shall be constructed of 16 gauge steel and shall<br />
be equipped with a hinged and removable front-access<br />
door and shall house all combustion related safeties and<br />
control logic. The Burner Panel shall be designed to interface<br />
directly with the ISN Millennium Control Center<br />
Panel to provide integrated burner control for the chillerheater.<br />
The Burner Control Panel shall be premounted<br />
and prewired to the chiller-heater and shall include the<br />
following components:<br />
• Honeywell RM 7840L flame safeguard<br />
• Burner On/Off switch<br />
• 115V control power transformer<br />
• Motor starters, complete with current overload protection<br />
for blower motor and remote oil plump (if<br />
used)<br />
• Electrical transient suppressors<br />
• Alarm bell<br />
• Fresh air damper open/close contacts<br />
• Flame failure indication contacts<br />
• Exhaust gas temperature limit switch<br />
NOTE: Remote exhaust gas temperature sensor to be<br />
field wired and installed in exhaust breaching<br />
• Indicating lamps, labeled as follows:<br />
• Call for Operation<br />
• Ignition On<br />
• Main Fuel<br />
Millennium Control Center Panel – The ISN Millennium<br />
Control Center enclosure shall be NEMA 1 and be<br />
equipped with hinged access door with lock and key. All<br />
temperature sensors, pressure transducers, and other<br />
control devices necessary to sense unit operating parameters<br />
to be factory-mounted and wired to panel. The ISN<br />
Millennium Control Center Panel shall include a 40 character<br />
alphanumeric display showing all system parameters<br />
in the English language with numeric data in English<br />
(or metric) units (°F, PSIA, or °C, KPa respectively).<br />
115V control voltage will be supplied through a 1 KVA<br />
power transformer located in the Power Panel and will<br />
be factory wired to the ISN Millennium Control Center<br />
Panel.<br />
Terminal blocks will be provided for all external safety<br />
and control interlocks.<br />
The operating program shall be stored in non-volatile<br />
memory (EPROM) to eliminate chiller failure due to AC<br />
power failure/battery discharge. In addition, programmed<br />
setpoints shall be retained in lithium battery-backed RTC<br />
memory for a minimum of 5 years.<br />
All wiring and control interlocks between the ISN Millennium<br />
Control Center Panel and the Burner Control Panel<br />
shall be factory installed and tested prior to unit shipment.<br />
System Operating Information – During normal operation<br />
the following operating parameters shall be accessible<br />
via the ISN Millennium Control Center Panel:<br />
• Return and leaving chilled-water temperatures<br />
• Return and leaving hot-water temperatures<br />
• Return and leaving condenser-water temperatures<br />
• First-stage generator pressure<br />
• First-stage generator temperature<br />
• Refrigerant temperature<br />
• Solution temperature<br />
• Indication of refrigerant/solution/purge pump/<br />
manual dilutions cycle operation<br />
• Operating hours<br />
• Number of starts<br />
• Number of Purge Cycles (last 7 days and total cumulative)<br />
• Burner firing-rate command (in %)<br />
Capacity Control – The ISN Millennium Control Center<br />
Panel shall automatically control the burner firing rate<br />
to maintain the programmed leaving chilled water or hot<br />
water setpoints for cooling or heating loads ranging from<br />
30% to 100% of design. The burner firing rate shall also<br />
be adjustable manually from the ISN Millennium Control<br />
Center Panel to any setting between 30% and maximum<br />
when automatic operation is not desired and when the<br />
burner firing rate is not being inhibited by a specific operating<br />
condition.<br />
Safety Shutdowns – Panel shall be pre-programmed<br />
to shut the unit down and close “safety shutdown” contacts<br />
under any of the following conditions:<br />
• Refrigerant- or Solution-pump thermal or current<br />
overload<br />
• Low refrigerant temperature<br />
• First-stage generator high temperature or pressure<br />
• First-stage generator low solution level<br />
• Burner alarm indication<br />