FORM 155.17-EG4<br />

ply; non-fused disconnect switch; motor starters, complete<br />

with current and thermal overload protection, for<br />

solution pump, refrigerant pump, and purge pump (current<br />

overloads only); and a 115VAC 50/60 Hz Control<br />

Power Transformer.<br />

Burner Control Panel – The Burner Control Panel enclosure<br />

shall be constructed of 16 gauge steel and shall<br />

be equipped with a hinged and removable front-access<br />

door and shall house all combustion related safeties and<br />

control logic. The Burner Panel shall be designed to interface<br />

directly with the ISN Millennium Control Center<br />

Panel to provide integrated burner control for the chillerheater.<br />

The Burner Control Panel shall be premounted<br />

and prewired to the chiller-heater and shall include the<br />

following components:<br />

• Honeywell RM 7840L flame safeguard<br />

• Burner On/Off switch<br />

• 115V control power transformer<br />

• Motor starters, complete with current overload protection<br />

for blower motor and remote oil plump (if<br />

used)<br />

• Electrical transient suppressors<br />

• Alarm bell<br />

• Fresh air damper open/close contacts<br />

• Flame failure indication contacts<br />

• Exhaust gas temperature limit switch<br />

NOTE: Remote exhaust gas temperature sensor to be<br />

field wired and installed in exhaust breaching<br />

• Indicating lamps, labeled as follows:<br />

• Call for Operation<br />

• Ignition On<br />

• Main Fuel<br />

Millennium Control Center Panel – The ISN Millennium<br />

Control Center enclosure shall be NEMA 1 and be<br />

equipped with hinged access door with lock and key. All<br />

temperature sensors, pressure transducers, and other<br />

control devices necessary to sense unit operating parameters<br />

to be factory-mounted and wired to panel. The ISN<br />

Millennium Control Center Panel shall include a 40 character<br />

alphanumeric display showing all system parameters<br />

in the English language with numeric data in English<br />

(or metric) units (°F, PSIA, or °C, KPa respectively).<br />

115V control voltage will be supplied through a 1 KVA<br />

power transformer located in the Power Panel and will<br />

be factory wired to the ISN Millennium Control Center<br />

Panel.<br />

Terminal blocks will be provided for all external safety<br />

and control interlocks.<br />

The operating program shall be stored in non-volatile<br />

memory (EPROM) to eliminate chiller failure due to AC<br />

power failure/battery discharge. In addition, programmed<br />

setpoints shall be retained in lithium battery-backed RTC<br />

memory for a minimum of 5 years.<br />

All wiring and control interlocks between the ISN Millennium<br />

Control Center Panel and the Burner Control Panel<br />

shall be factory installed and tested prior to unit shipment.<br />

System Operating Information – During normal operation<br />

the following operating parameters shall be accessible<br />

via the ISN Millennium Control Center Panel:<br />

• Return and leaving chilled-water temperatures<br />

• Return and leaving hot-water temperatures<br />

• Return and leaving condenser-water temperatures<br />

• First-stage generator pressure<br />

• First-stage generator temperature<br />

• Refrigerant temperature<br />

• Solution temperature<br />

• Indication of refrigerant/solution/purge pump/<br />

manual dilutions cycle operation<br />

• Operating hours<br />

• Number of starts<br />

• Number of Purge Cycles (last 7 days and total cumulative)<br />

• Burner firing-rate command (in %)<br />

Capacity Control – The ISN Millennium Control Center<br />

Panel shall automatically control the burner firing rate<br />

to maintain the programmed leaving chilled water or hot<br />

water setpoints for cooling or heating loads ranging from<br />

30% to 100% of design. The burner firing rate shall also<br />

be adjustable manually from the ISN Millennium Control<br />

Center Panel to any setting between 30% and maximum<br />

when automatic operation is not desired and when the<br />

burner firing rate is not being inhibited by a specific operating<br />

condition.<br />

Safety Shutdowns – Panel shall be pre-programmed<br />

to shut the unit down and close “safety shutdown” contacts<br />

under any of the following conditions:<br />

• Refrigerant- or Solution-pump thermal or current<br />

overload<br />

• Low refrigerant temperature<br />

• First-stage generator high temperature or pressure<br />

• First-stage generator low solution level<br />

• Burner alarm indication<br />

YORK INTERNATIONAL<br />