01.07.2015 Views

Connection schemes Sepam 1000+ series 40 - Trinet

Connection schemes Sepam 1000+ series 40 - Trinet

Connection schemes Sepam 1000+ series 40 - Trinet

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Protection functions<br />

Setting ranges<br />

Functions Settings Time delay<br />

Directional earth fault, according to Io projection (type 1)<br />

Characteristic angle -45°, 0°, 15°, 30°, 45°, 60°, 90°<br />

Iso set point 0,1 to 15 Ino Definite time Inst.: 0.05 s to 300 s<br />

Vso set point<br />

2 to 80 % of Un<br />

Memory time Tomem duration 0; 0.05 s to 300 s<br />

Vomem validity set point<br />

0; 2 to 80 % of Un<br />

Directional earth fault, according to Io magnitude (type 2)<br />

Characteristic angle -45°, 0°, 15°, 30°, 45°, 60°, 90°<br />

Tripping curve<br />

Reset time<br />

Definite time<br />

DT<br />

SIT, LTI, VIT, EIT, UIT (1)<br />

DT<br />

RI<br />

DT<br />

CEI, SIT/A,LTI/B, VIT/B, EIT/C DT or IDMT<br />

IEEE: MI (D), VI (E), EI (F)<br />

DT or IDMT<br />

IAC: I, VI, EI<br />

DT or IDMT<br />

Iso set point 0.1 to 15 Ino Definite time Inst.: 0.05 s to 300 s<br />

0.1 to 1 Ino IDMT 0.1 s to 12.5 s at 10 Iso<br />

Vso set point<br />

2 to 80 % of Un<br />

Reset time Definite time (DT: timer hold) Inst.: 0.05 s to 300 s<br />

IDMT (IDMT: reset time)<br />

0.5 s to 300 s<br />

Active overpower<br />

1 to 120 % of Sn<br />

Thermal overload Rate 1 Rate 2<br />

Negative sequence factor 0 - 2.25 - 4.5 - 9<br />

Time constant Heat rise T1: 5 to 120 mn T1: 5 to 120 mn<br />

Cooling T2: 5 to 600 mn T2: 5 to 600 mn<br />

Alarm and trip set points<br />

50 to 300 % of rated thermal capacity used<br />

Cold curve change factor 0 to 100 %<br />

Rate change condition<br />

by logic input<br />

by Is setting from 0.25 to 8 Ib<br />

Maximum equipment temperature 60 to 200 °C<br />

Phase undercurrent<br />

0.15 to 1 Ib 0.05 s to 300 s<br />

Excessive starting time/locked rotor<br />

0.5 Ib to 5 Ib ST start time 0.5 s to 300 s<br />

LT and LTS time delays<br />

0.05 s to 300 s<br />

Starts per hour<br />

Starts per period 1 to 60 Period 1 to 6 h<br />

Consecutive starts 1 to 60 time between starts 0 to 90 mn<br />

Temperature (RTDs)<br />

Alarm and trip set points<br />

0 to 180 °C (or 32 to 356 °F)<br />

Positive sequence undervoltage<br />

15 to 60 % de Unp 0.05 s to 300 s<br />

Remanent undervoltage<br />

5 to 100 % of Unp 0.05 s to 300 s<br />

Phase-to-phase undervoltage<br />

5 to 100 % of Unp, 5 to 100 % of Vnp (4) 0.05 s to 300 s<br />

Phase-to-neutral undervoltage<br />

5 to 100 % of Vnp 0.05 s to 300 s<br />

Overvoltage phase-to-phase phase-to-neutral (4)<br />

50 to 150 % of Unp 50 to 150 % of Vnp 0.05 s to 300 s<br />

Neutral voltage displacement<br />

2 to 80 % of Unp 0.05 s to 300 s<br />

Negative sequence overvoltage<br />

1 to 50 % of Unp Inst.: 0.05 s to 300 s<br />

Overfrequency<br />

50 to 53 Hz or 60 to 63 Hz 0.1 s to 300 s<br />

Underfrequency<br />

45 to 50 Hz or 55 to 60 Hz 0.1 s to 300 s<br />

Rate of change of frequency<br />

0.1 to 10 Hz/s Inst.: 0.15 s to 300 s<br />

Reminder: In current, Unp rated voltage and Ino current are general settings that are made at the time of <strong>Sepam</strong> commissioning.<br />

They are given as the values on the measurement transformer primary windings.<br />

In is the current sensor rated current (CT rating) (adjustable from 1 A to 6250 A).<br />

Unp is the rated phase-to-phase voltage of the voltage sensor primary windings (adjustable from 220 V to 250 kV).<br />

Ino is the core balance CT current rating.<br />

Ib is the current which corresponds to the equipment power rating, adjustable from 0.4 to 1.3 In.<br />

The current, voltage and frequency values are set by direct entry of the values (resolution: 1 A, 1 V, 1 Hz, 1°C or F).<br />

(1) tripping as of 1.2 Is.<br />

(2) with ACE 990 interface for core balance CT with ratio n of 50 to 1500 turns.<br />

(3) table of In values in Amps: 25, 50, 100, 125, 133, 200, 250, 320, <strong>40</strong>0, 500, 630, 666, 1000, 1600, 2000, 3150.<br />

(4) on <strong>series</strong> <strong>40</strong> only.<br />

Schneider Electric<br />

15

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!