Parameter and protection<br />

settings<br />

Program logic<br />

Each <strong>Sepam</strong> <strong>1000+</strong> has program logic by default according to the chosen type<br />

(S20, S<strong>40</strong>, T20,…) as well as messages for the different signal lamps.<br />

The functions are assigned according to the most frequent use of the unit. The<br />

parameter setting and/or marking may be customized if required using the SFT 2841<br />

software tool.<br />

Example of parameter setting: <strong>Sepam</strong> S20 equipped with the optional MES114 module<br />

IS (2) Outputs Signal lamps Associated<br />

functions<br />

Functions 01 02 03 04 011 012 013 014 L1 L2 L3 L4 L5 L6 L7 L8 L9<br />

Phase protection 50/51-1 # # # # # # Circuit breaker<br />

50/51-2 # # # # # # control<br />

Earth fault protection 50N/51N-1 # # # # # #<br />

50N/51N-2 # # # # # #<br />

Unbalance protection 46 # # # #<br />

Recloser 79 # #<br />

Open position l11 # # Trip circuit<br />

Closed position l12 # # supervision<br />

Receive blocking<br />

input<br />

l13 # Logic<br />

discrimination<br />

Line disconnector l14 #<br />

position open (1)<br />

Tripping by external l21 # #<br />

protection<br />

l22<br />

l23<br />

l24<br />

Inhibit remote control l25 # Remote control<br />

SF6 pressure drop l26 # #<br />

Transmit blocking # # Logic<br />

discrimination<br />

"Pick-up" signal # Disturbance<br />

recording<br />

triggering<br />

Watchdog # #<br />

Output<br />

O1 - tripping<br />

O2 - inhibit closing<br />

O3 - transmit BI<br />

O4 - watchdog<br />

O11 - close order<br />

O12 - phase fault indication<br />

O13 - earth fault indication<br />

O14 - permanent fault<br />

(1) or disconnected position.<br />

(2) in service.<br />

Signal lamps<br />

L1 - I > 51<br />

L2 - I >> 51<br />

L3 - lo > 51N<br />

L4 - lo >> 51N<br />

L5 - ext<br />

L6 -<br />

L7 - off<br />

L8 - on<br />

L9 - Trip<br />

Schneider Electric<br />

31