Characteristics<br />
Environmental characteristics<br />
Isolation<br />
Dielectric withstand at power frequency CEI 60255-5 2 kVrms - 1mn (1)<br />
1.2 / 50 µs impulse wave CEI 60255-5 5 kV (2)<br />
Electromagnetic compatibility<br />
Fast transient bursts CEI 60255-22-4 class IV<br />
CEI 61000-4-4<br />
level IV<br />
1 MHz damped oscillating wave CEI 60255-22-1 class III<br />
Immunity to radiated fields CEI 61000-4-3 level III 10 V/m<br />
Immunity to conducted RF disturbances CEI 61000-4-6 level III 10 V<br />
Electrostatic discharge CEI 60255-22-2 class III 6 kV / 8 kV (contact / air)<br />
CEI 61000-4-2 level III<br />
Conducted disturbance emission EN 55022 / CISPR 22 class B on aux. supply (3)<br />
Disturbing field emission EN 55022 / CISPR 22 class A<br />
(4)<br />
Mechanical robustness<br />
Degree of protection CEI 60529 IP 52 (7) on front panel<br />
other sides closed<br />
(except for rear IP 20)<br />
Vibrations CEI 60255-21-1 class II (5)<br />
Shocks / jolts CEI 60255-21-2 class II (5)<br />
Earthquakes CEI 60255-21-3 class II (5)<br />
Fire resistance CEI 60695-2-1 glow wire 650 °C<br />
Climatic withstand<br />
Operation CEI 60068-2-1 et 2 -25 °C à + 70 °C<br />
Storage CEI 60068-2-1 et 2 -25 °C à +70 °C<br />
Damp heat CEI 60068-2-3 93 % HR à <strong>40</strong> °C,<br />
56 days (storage)<br />
10 days (operation)<br />
Effect of corrosion CEI-68054-4 class I<br />
Certification<br />
CE<br />
UL508 (6)<br />
(1) except for communication 1 kVrms.<br />
(2) except for communication 3 kV common mode, 1 kV differential mode.<br />
(3) generic EN 50081-1 standard.<br />
(4) generic EN 50081-2 standard.<br />
(5) intrinsic withstand of product, excluding support equipment.<br />
(6) <strong>series</strong> <strong>40</strong>: please consult us.<br />
(7) a gasket delivered with the product can be used to ensure NEMA12 withstand.<br />
Schneider Electric<br />
35