11.07.2015 Views

Profibus-DP

Profibus-DP

Profibus-DP

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Telegram 2The second telegram from the <strong>DP</strong> master also indicates a Write cycle, butthe stamp number is now set to 2. The data byte would contain theparameter number for the parameter that is to be written to.Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0Value 0 X X X 0 0 1 0 0 0 0 0 1 0 1 1Data word: 0x020B Stamp number = 2 Parameter number = 11When the second telegram has been received and processed in the <strong>DP</strong> node,it is mirrored in the non-cyclic IN word.Telegram 3The third telegram from the <strong>DP</strong> master has the stamp number set to 3. Thedata bits contain the data high byte for the parameter being written to.Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0Value 0 X X X 0 0 1 1 0 0 0 0 1 0 1 1Data word: 0x030B Stamp number = 3 Data high byte = 2816When the first telegram has been received and processed in the <strong>DP</strong> node, itis mirrored in the non-cyclic IN word.<strong>Profibus</strong>–<strong>DP</strong>Issue code: pbnu2 25