10Publication# 105331revAPrefilter Removal ProcedureWARNINGSecure electrical power and supply air to <strong>Axiom</strong> unit prior to performing the Prefilter Removal Procedure.1. Secure electrical power and supply air to the <strong>Axiom</strong> unit.2. Loosen Cover Lock set screw and remove <strong>Axiom</strong> Cover.3. With an M3 allen wrench, loosen the two captive screws located next to the pilot valve/s. These hold the internal air interface platein place. (See Fig. 1)4. Carefully lift the internal air interface plate to expose the prefilter (see Fig. 2).5. With an M8 allen wrench, remove the prefilter (See Fig. 3). Inspect and clean as necessary.6. Re-install prefilter and torque to 25 - 30 in.lbs (2.8 - 3.4Nm).7. Re-install the internal air interface plate and torque screws to 25 - 30 in.lbs (2.8 - 3.4Nm).8. Install unit cover and place unit back into service.Fig. 1 Fig. 2Fig. 3<strong>StoneL</strong>Factory phone +1 (218) 739-5774