11.07.2015 Views

LIMIT SWITCH Axiom - AX - StoneL

LIMIT SWITCH Axiom - AX - StoneL

LIMIT SWITCH Axiom - AX - StoneL

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

8Publication# 105331revAFoundation Sensing & Communications Module SpecificationsSpecificationsCommunication Protocol: Foundation Fieldbus (H1)Configuration:(2) Discrete Inputs (Sensors)(2) Discrete Outputs (Piezo Valves)Function Blocks 2 DI; 2 DOExecution TimeMaximum 30ms per DI and DOVoltage:9-32 VDC (Bus Voltage)Output Voltage:6.5 VDCMax. Output Current: 2.0mA @ 6.5 VDCCurrent Draw:16mADevices per Network Maximum of 16 devices recommendedStandard Channel AssignmentsChannel 1 (DI1) - Discrete Input 1 (Red LED);Channel 2 (DI2) - Discrete Input 2 (Green LED);Channel 3 (DO1) - Discrete Output 1 (OUT 1);Channel 4 (DO2) - Discrete Output 2 (OUT 2);1 = True; 0 = False1 = True; 0 = False1 = True; 0 = False1 = True; 0 = FalseSpecial Channel AssignmentsChannel 8 (DO1) - Discrete Output 1 (OUT 1) with state report from Discrete Input 1 (READBACK_D)Channel 9 (DO2) - Discrete Output 2 (OUT 2) with state report from Discrete Input 2 (READBACK_D)Valve Control Single Block ModeChannel 10 (DO1) - Discrete Output 1 (OUT 1) with state report Discrete Inputs 1&2 (READBACK_D):READBACK_D Values:0 = None1 = Discrete Input 1 is True2 = Discrete Input 2 is True3 = Both Discrete Inputs 1&2 are True<strong>StoneL</strong>Factory phone +1 (218) 739-5774

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!