I/O <strong>Module</strong> Introduction<strong>ADAM</strong>-5018 7-channel thermocouple input moduleThe <strong>ADAM</strong>-5018 is a 16-bit, 7-channel thermocouple input module thatfeatures programmable input ranges on all channels. It acceptsmillivolt inputs (±15 mV, ±50 mV, ±100 mV, ±500 mV), voltage inputs (±1V, ±2.5 V), current input (±20 mA, requires 125 ohms resistor) andthermocouple input (J, K, T, R, S, E, B).The module forwards the data to the host computer in engineering units(mV, V, mA or temperature °C). An external CJC on the plug-in terminal isdesigned for accurate temperature measurement.<strong>ADAM</strong>-5018Figure 16: <strong>ADAM</strong>-5018 module frontal view<strong>ADAM</strong>-<strong>5000</strong> <strong>Series</strong> I/O <strong>Module</strong> User’s <strong>Manual</strong> P.23